Atom B Series VRF 50/60Hz
Figure 2‐1.3: 60 model piping diagram
Low pressure
switch
Key components: 
1. Oil separator:   
Separates oil from gas refrigerant pumped out of the compressor and quickly returns it to the compressor. Separation 
efficiency is up to 99%. 
2. Gas‐liquid separator:   
Stores liquid refrigerant and oil to protect compressor from liquid hammering. 
3. Electronic expansion valve (EXV): 
Controls refrigerant flow and reduces refrigerant pressure. 
4. Four‐way valve(ST1):   
Controls refrigerant flow direction. Closed in cooling mode and open in heating mode. When closed, the heat exchanger 
functions as a condenser; when open, the heat exchanger functions as an evaporator. 
5. High and low pressure switches:   
Regulate system pressure. When system pressure rises above the upper limit or falls below the lower limit, the high or 
low pressure switches turn off, stopping the compressor. After 5 minutes, the compressor restarts. 
 
10 
   
 
Gas pipe
4 way valve
Temperature
sense
Oil seperator
Compressor
42
High pressure
switch
Silencer(Reserved)
Oil return capiliary
 
 
Temperature sense
DC motor
 
Liquid pipe
Filter
Refrigerant
radiator
modile
Temperature sense
Distributor
Temperature sense
   
 
 