Midea ATOM B Series Service Manual page 21

Commercial air conditioners

Advertisement

Atom B Series VRF 50/60Hz
5.4 Compressor and Inverter Module Protection Control 
This control protects the compressors from abnormally high currents and protects the inverter modules from abnormally 
high temperatures.   
   
5.5 Disable Cooling Control 
When  the  outdoor  ambient  temperature  drops  below  or  equal  to  -15°C,  cooling  mode  is  disabled  to  prevent  low 
compression ratios which can result in insufficient compressor internal oil lubrication, and prevent humid compressed in low 
superheat of compressor bottom conditions. When the outdoor ambient temperature rises above or equal to -14°C, the 
compressor enters re-start control.   
Outdoor ambient temperature 
 
20 
   
Figure 3‐5.4: Compressor current protection control
Normal operation
Current ≥ Current
max
Compressor current protection, error code P3 is displayed
Figure 3‐5.6: Disable heating control
Cooling operation 
o
 -15
C
 
 
 
Current < Current
 
Outdoor ambient temperature ≥ -14
Units stop
 
max
 
o
 
 