Dantel 05202 Installation & Operation Manual

Small central office master alarm system

Advertisement

Quick Links

About this Practice:
This practice has been reissued to:
• Update to reflect Y2K compliance.
Reissued Practices: Updated and
new content can be identified by a
banner in the right margin.
Issue date: February 1999
Copyright 1999 by Dantel, Inc. • Dantel is a registered trademark of Dantel, Inc. • ISO 9001 Registered
S
MALL
M
ASTER

Table of Contents

Ordering Information ........................................................................... 2
Introduction .......................................................................................... 3
Application Information ....................................................................... 5
Installation ............................................................................................ 7
Support Documentation ..................................................................... 43
Warranty ............................................................................................. 46
CAUTION
Install or remove modules from the shelf only when the power is off.
If you install a module in the shelf with the power on, the internal
circuitry may suffer damage and the product warranty will be void.
Remove and install circuit boards only in a static-safe environment
(use antistatic wrist straps, smocks, footwear, etc.).
Keep circuit boards in their antistatic bags when they are not in use.
Do not ship or store circuit boards near strong electrostatic, electromag-
netic, magnetic, or radioactive fields.
For more complete information on electrostatic discharge safety
precautions, refer to Bellcore
Printed in the U.S.A.
I
NSTALLATION
05202-0299 <90-00046>
05202
C
O
ENTRAL
A
S
LARM
TM
Technical Reference # TR-NWT-000870.
& O
M
PERATION
ANUAL
FFICE
YSTEM

Advertisement

loading
Need help?

Need help?

Do you have a question about the 05202 and is the answer not in the manual?

Questions and answers

Summary of Contents for Dantel 05202

  • Page 1: Table Of Contents

    For more complete information on electrostatic discharge safety Issue date: February 1999 precautions, refer to Bellcore Technical Reference # TR-NWT-000870. Copyright 1999 by Dantel, Inc. • Dantel is a registered trademark of Dantel, Inc. • ISO 9001 Registered Printed in the U.S.A.
  • Page 2: Ordering Information

    ORDERING INFORMATION NOTE: This section lists the different options available for this product. To order any of the avail- able options, contact Dantel Inside Sales through our toll-free number, 1-800-432-6835. OPTION NUMBER FEATURES A18-05202-30 256 Discrete Alarm Points, 16 Control Points, 15 TBOS Ports, Writing Shelf...
  • Page 3: Introduction

    The operating instructions in the practices will provide a useful reference to the user who needs more details than given in the turn-up procedure in the Installation section. 05202-0299 <90-00046>...
  • Page 4 INTRODUCTION 05202-0299 <90-00046>...
  • Page 5: Application Information

    The MAP and Status Monitor require a database to operate. These databases are configured using a computer running T/Shell software and downloaded to the modules from the computer. The Fuse Module provides fused power to each slot of the shelf. 05202-0299 <90-00046>...
  • Page 6 APPLICATION INFORMATION 05202-0299 <90-00046>...
  • Page 7: Installation

    ♦ 46001 Status Monitor ♦ 05202 Equipment Shelf WIRING ♦ A18-05202-XX Block Diagram ♦ DT-05202-30 Master Alarm System Interconnection draw- ings SWITCH AND STRAP SETTINGS ♦ 44124-00 Data Channel Termination Module ♦ 46001-03 Status Monitor ♦ 46009-02 Multiple Alarm Transmitter ♦...
  • Page 8 INSTALLATION 05202-0299 <90-00046>...
  • Page 9 Make sure that the bracket positions match the rack before reat- taching the slides to the shelf. . 1 - M , 41060 W OUNTING ONFIGURATIONS RITING HELF DOUBLE MOUNTED PROJECTION (Recommended) FLUSH MOUNTED SINGLE MOUNTED PROJECTION 05202-0299 <90-00046>...
  • Page 10 HOLES THREADED FLANGE THREADED FLANGE HOLES HOLES SLOTTED SLOTTED HOLE HOLE EQUIPMENT RACK EQUIPMENT RACK MOUNTING BRACKET SLOTTED SLOTTED HOLE MOUNTING BRACKET HOLE TOP VIEW 23" STATUS MONITOR THREADED FLANGE THREADED FLANGE HOLES HOLES SLOTTED SLOTTED HOLE HOLE 05202-0299 <90-00046>...
  • Page 11 To ensure expedient processing for your order, provide a pur- chase order number and shipping and billing information when requesting an RMA number. Also, when the units are returned to Dantel, include a description of the failure symptoms for each unit returned. Send returned materials to: Dantel, Inc.
  • Page 12 From the rear of the bay, install the other ESD stud and lockwasher into the frame rail next to the equipment shelf. Secure tightly, ensuring proper grounding of the ESD stud. Place ESD label next to the ESD stud. . 4 - M , 41075 400-T OUNTING ONFIGURATION OUNTING 05202-0299 <90-00046>...
  • Page 13 INSTALLATION WIRING Wire the Small Central Office Master Alarm System to external equipment as required. Use the A18-05202-XX and DT-05202-30 drawings as references for making connections to the Dantel equipment. 05202-0299 <90-00046>...
  • Page 14 INSTALLATION 05202-0299 <90-00046>...
  • Page 15 WITCH OCATIONS ODUJLE .2 .4.8 1.5 3 6 12 OPEN NL 1 2 4 8 1 2 4 8 1 2 4 8 OPEN OPEN 150 600 1200 .1.2 .4.8 1.5 3 6 12 OPEN OPEN 8 16 05202-0299 <90-00046>...
  • Page 16 The data rate for the data port defaults to 1200 baud. The data rate can be changed to 9600 baud using printer syntax com- mands. NOTE: For additional information regarding this and other printer ssyntax commands, or for further details about switch settings, refer to the 46001 Status Monitor Practice. 05202-0299 <90-00046>...
  • Page 17 INSTALLATION . 7 - B , 46001 S OARD AYOUT TATUS OLNITOR 05202-0299 <90-00046>...
  • Page 18 Reinstall the power supply subassembly board, insuring that each pin of the board to board connector is in the proper position. Rein- stall the module into the 46001 housing. . 8 - S , 46062 WITCH AND TRAP OCATIONS LOW BATTERY INDICATOR 05202-0299 <90-00046>...
  • Page 19 3 for the MAT in slot 2; 5 for the MAT in slot 3 and so on. NOTE: For additional details about the switch and strap settings, refer to the 46009 Multiple Alarm Transmitter Practice in the Appendix. 05202-0299 <90-00046>...
  • Page 20 MEMORY BOARD SUBASSEMBLY MOUNTS ON MAIN BOARD OVER S6 4 3 2 1 SUBASSEMBLY MOUNTING AREA 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 05202-0299 <90-00046>...
  • Page 21 SLOT 4 SLOT 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 NOTE: Fig. 10 shows two typical addressing schemes. For further addressing options, refer to the 46009 Operations Manual. 05202-0299 <90-00046>...
  • Page 22 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SWITCH 4 SWITCH 1 SWITCH 3 SWITCH 2 05202-0299 <90-00046>...
  • Page 23 2 for the Smart MAC in slot 11. The Smart MAC will communicate with the MAP at 9600 baud using DCPF protocol. . 12 - S , 46023-14 SMAC WITCH AND TRAP OCATIONS UP - OFF OUT IN 05202-0299 <90-00046>...
  • Page 24 . 13 - S , 46028 CPM WITCH AND TRAP OCATIONS S 104 S 102 S 103 S 101 POINT PROGRAMMING SWITCH OPTION BOARD UP = OFF DOWN = ON NORM SUBASSEMBLY MOUNTING AREA UP = OFF DOWN - ON 05202-0299 <90-00046>...
  • Page 25 Master/Slave Straps - Leave open (remove straps or place on one pin). Set the receive and transmit pads as required. Refer to Table A. NOTE: For additional details about the switch and strap settings, refer to the 49013 202 Tone Modem Subassembly Practice. 05202-0299 <90-00046>...
  • Page 26 XMT PAD XMT Pad IN (output adjustable from -20 to -40 dBm) Jumpers parallel to P5 (See Fig. 15) XMT Pad OUT (output adjustable from -1 to -20 dBm) Jumpers perpendicular to P5 (See Fig. 15) Normal Operation 05202-0299 <90-00046>...
  • Page 27 To configure the database of the 46020 Multiple Alarm Proces- sor (MAP) requires a T/Shell software program with the -41 MAP Editor Module (Dantel part number A22-46512-XX). The software programs are not supplied with the shelf. To use the software the minimum requirements are an IBM PC/...
  • Page 28 MAP’s database. For additional information, refer to the -41 MAP Editor Module documentation. Step 1 Turn on the power to your computer and monitor. Wait for the DOS prompt (such as C:\) to appear..CONTINUED 05202-0299 <90-00046>...
  • Page 29 Enter a name and press the ENTER key. At the bottom of the screen, a message will appear asking Not there. Wish to add (Y/N)? Type Y. A window will appear to select the number of alarm and control displays the 46020 MAP can have..CONTINUED 05202-0299 <90-00046>...
  • Page 30 Type an address for displays 65-128 if used or type N if not used. Press ENTER Press ENTER to select No, do not disable point 64 device fail- ures. Step 11 Highlight EDIT RESPONDER PORT and press ENTER to se- lect. Highlight EDIT BAUD and press ENTER..CONTINUED 05202-0299 <90-00046>...
  • Page 31 SELECT DATA PORT. You are now going to configure each of the ports of the Smart MAC. NOTE: Steps 17 through 20 only apply to port 1 of the Smart MAC in slot 10..CONTINUED 05202-0299 <90-00046>...
  • Page 32 Return to the DATA PORT MENU window. Step 23 Repeat Steps 21 and 22 until all ports are entered. When all the addresses are entered, select QUIT in the DATA PORT MENU window and press ENTER..CONTINUED 05202-0299 <90-00046>...
  • Page 33 Step 25 Connect a cable from the RS-232 (COM 1) port of your computer to the printer port of the MAP in the Dantel master shelf (con- nector C). Disconnect, temporarily, any wiring from the MAP Printer Port to the Status Monitor.
  • Page 34 INSTALLATION 05202-0299 <90-00046>...
  • Page 35 Refer to the checkout procedure (Table B) and Tables C through F for set-up of the 44124 Data Station Termination module. Generate alarms and verify each is reported correctly. Operate control points and verify proper operation. 05202-0299 <90-00046>...
  • Page 36 INSTALLATION B - C , 44124 M ABLE HECKOUT ROCEDURE ODULE . ) s . ) s . ) s ) t i 05202-0299 <90-00046>...
  • Page 37 2.60 2.20 2.90 2.35 3.10 2.50 3.25 2.60 3.60 2.65 4.00 2.70 4.15 2.75 4.30 2.80 4.45 2.85 4.60 If the calculated values of Slope (SL) fall between settings, use the lower setting indicated NOTE: by the table. 05202-0299 <90-00046>...
  • Page 38 TOTAL (VALUES in dB) 0.00 0.35 1.05 1.75 2.45 3.15 3.85 4.55 5.25 5.95 6.65 7.35 8.05 8.75 9.45 10.15 If calculated values of Height (HT) fall between settings, use the lower setting NOTE indicated by the table. 05202-0299 <90-00046>...
  • Page 39 ETTINGS FOR LOSS AT 2504 Hz WITH 1004 Hz FOR REFERENCE BW SETTING SWITCH REFERENCE S7-5(1) S7-6(2) S7-7(4) S7-8(8) TOTAL If calculated values of Bandwidth (BW) fall between settings, use NOTE: the lower setting indicated by the table. 05202-0299 <90-00046>...
  • Page 40 13 0.00 0.52 0.68 0.87 1.07 1.44 1.98 2.99 3.55 3.90 4.33 4.58 5.03 5.37 5.63 5.72 14 0.00 0.56 0.73 0.93 1.15 1.55 2.13 3.22 3.83 4.20 4.67 4.93 5.41 5.79 6.07 6.16 15 0.00 0.60 0.78 1.00 1.23 1.66 2.28 3.45 4.10 4.50 5.00 5.28 5.80 6.20 6.50 6.60 05202-0299 <90-00046>...
  • Page 41 For repairs and emergency replacements, obtain a “Returned Material Authori- zation” (RMA) number by calling Dantel and asking for the Customer Returns Representative. Please to provide a purchase order number, and shipping and billing information when requesting an RMA number.
  • Page 42 INSTALLATION 05202-0299 <90-00046>...
  • Page 43: Support Documentation

    46009 Multiple Alarm Transmitter 46020-41 Multiple Alarm Processor 46023-14 Smart Multiple Alarm Combiner 46028 Control Point Module 48001 Fuse Module 49008 Current Loop Subassembly 49013 202 Tone Modem Subassembly T/Shell Application Manager T/Shell with -41 MAP Editor Module 05202-0299 <90-00046>...
  • Page 44 APPENDIX 05202-0299 <90-00046>...
  • Page 45 NOTES 05202-0299 <90-00046>...
  • Page 46: Warranty

    To ensure expedient processing of your order, provide a purchase order number and shipping and billing information when requesting an RMA number. Also, when the units are returned to Dantel, include a descrip- tion of the failure symptoms for each unit returned. Send defective equipment to: Dantel, Inc.