Replacing Filters

Filters can be removed and installed from either side of the
unit. Install new filters in units that have one fan as follows:
1. Remove the side access panel (retain screws).
2. Remove the filter retainer clip (see Fig. 36).
3. Remove old filters by lifting and tilting them out of the fil-
ter track. (See Fig. 12 and 37.)
4. Reverse the procedure to install new filters.
To install new filters in larger units that have 2 fans, follow
the preceding steps, but use the factory-supplied filter hook
to slide filters within reach for removal. The filter hook is
shipped inside the unit in the filter track.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this CAUTION can result in premature
wear and damage to equipment.
DO NOT OPERATE THE UNIT WITHOUT THE
RETURN AIR FILTERS IN PLACE.
Dirt and debris can collect on heat exchangers and coils
possibly resulting in a small fire. Dirt buildup on
components can cause excessive current used resulting
in motor failure.
Fig. 36 — Remove Filter Retainer Clip
FASFHS150-180-01SI
Filter
Retainer
Clip
Specifications subject to change without notice.
Fig. 37 — Filter Removal/Replacement