Rated Indoor Airflow (Cfm); Unit Positioning; Unit Isolation - Carrier FAS150 Installation, Start-Up And Service Instructions Manual

Packaged air-handling units with r-410a refrigerant 60 hz
Table of Contents

Advertisement

TXV
Remove Foam Block
LEGEND
TXV — Thermostatic Expansion Valve
Fig. 3 — Foam Block Location

Rated Indoor Airflow (cfm)

Tables 5-7 list the rated indoor airflow used for the AHRI
(Air-Conditioning, Heating, and Refrigeration Institute)
efficiency rating for the units covered in this document.
Table 5 — CAS****G/H/MN with FAS150-180
MODEL NUMBER
CAS150G/H/M/N — FAS150
CAS180G/H/M/N — FAS180
Table 6 — CAS****T/U with FAS150-180
MODEL NUMBER
CAS150T/U — FAS150
CAS180T/U — FAS180
Table 7 — CHS with FHS180
MODEL NUMBER
CHS180 — FHS180
10
Coil
FULL LOAD AIRFLOW (CFM)
4400
6000
FULL LOAD AIRFLOW (CFM)
4400
5625
FULL LOAD AIRFLOW (CFM)
5625
REF
7' 11-1/2"
[2425.7]
Fig. 5 — Preferred Suspension Technique
Specifications subject to change without notice.

Unit Positioning

The unit can be mounted on the floor for vertical application
with return air entering the face of the unit and supply air
discharging vertically through the top of the unit. The unit
can also be applied in a horizontal arrangement with return
air entering horizontally and the supply air discharging hori-
zontally. When applying the unit in a horizontal arrange-
ment, ensure the condensate drain pan is located at the bot-
tom center of the unit for adequate condensate disposal.
See Fig. 4 for condensate connections for each unit
position.
Plug
Condensate Drain
LEGEND
Fig. 4 — Typical Unit Positioning
IMPORTANT: Do NOT attempt to install unit with return air
entering top panel of unit. Condensate will not drain from
unit.
Typical positioning and alternate return air locations are
shown in Fig. 4. Alternate return air locations can be used
by moving the unit panel from the alternate return air loca-
tion to the standard return air location. Refer to overhead
suspension accessory drawing (see Fig. 5) for preferred
suspension technique. The unit needs support underneath
to prevent sagging.

Unit Isolation

Where extremely quiet operation is essential, install isola-
tors between floor and base of unit, or between ceiling and
top section of unit.
Be sure that unit is level and adequately supported. Use
channels at front and sides of unit for reference points when
leveling.
IMPORTANT: Do not bury refrigerant piping underground.
3/8" Threaded Rod
(Field-Supplied)
NOTE: Dimensions in [ ] are millimeters.
Plug
Accessory Line
Alternate Air Intake and Discharge
Air Intake and Discharge
Overhead Suspension
Accessory with
Hot Water Coil
FASFHS150-180-01SI