MAINTENANCE

These items should be part of a routine maintenance pro-
gram, to be checked every month or two, until a specific
schedule for each can be identified for this installation:

Quarterly Inspection

(and 30 days after initial start)

INDOOR SECTION

Condenser coil cleanliness checked.
Return air filter replacement
Outdoor hood inlet filters cleaned
Fan shaft bearing locking collar tightness checked
Condensate drain checked
Heating
Power wire connections
Fuses ready
Manual-reset limit switch is closed
See Tables 12 and 13 for unit specific maintenance
checklists.

Seasonal Maintenance

These items should be checked at the beginning of each
season (or more often if local conditions and usage patterns
dictate):

AIR CONDITIONING

Condenser fan motor mounting bolts tightness
Compressor mounting bolts
Condenser fan blade positioning
Control box cleanliness and wiring condition
Wire terminal tightness
Refrigerant charge level
Evaporator coil cleaning
Evaporator blower motor amperage
24
Table 12 — Outdoor Unit Maintenance Checklist
Outdoor unit specific:
Clear away debris and vegetation near unit.
Inspect cabinet for damage. Replace
components that are damaged or severely
rusted.
Inspect electrical disconnect for proper
function. Repair or replace as necessary.
Inspect electrical wiring and connections.
Tighten loose connections. Inspect and
perform functional test of equipment as
needed to ensure proper function. Repair or
replace damaged or overheated components
and wiring.
Check refrigerant system subcooling and
superheat.
Inspect inside of unit. Clean if debris is
present.
Inspect condenser coil. Clean if dust, dirt, or
debris is present. Rinse unit with fresh
water.
Inspect motor and fan for damage. Make
sure fans spin freely.
NOTE(S):
a
The above list may not include all maintenance items. Inspection intervals may
vary depending on climate and opening hours. Consult your local dealer about
a service contact for seasonal inspections.
b
Monthly maintenance items and outdoor unit rinsing may be performed by the
customer. All other maintenance items and all service work must be performed
by a qualified service technician. Read all warning labels.
c
Do not use harsh chemicals or high pressure water on coils. More frequent rins-
ing is required near a sea coast.
d
Monthly rinsing of the condenser coil is recommended if the unit is located in a
corrosive climate.
Table 13 — Indoor Unit Maintenance Checklist
Indoor unit specific: (for accessories
refer to unit specific literature)
Inspect, clean, or replace air filter if dirty.
Inspect and clean blower assembly (includes
blower housing, wheel, and motor).
Lubricate shaft bearings.
Inspect internal and external cabinet. Clean
as needed.
Inspect electrical disconnect for proper
function. Repair or replace as necessary.
Inspect electrical components, wiring, and
connections. Tighten loose connections.
Repair or replace damaged components and
wiring.
Inspect evaporator coil. Clean if dust, dirt, or
debris is present.
Clean condensate pan, trap, and drain lines
(more frequent maintenance may be
required in humid climates — consult your
local HVAC dealer).
Inspect motor and fan for damage. Make
Inspect airflow system (ductwork). Check for
leaks and repair as needed.
NOTE(S):
a
The above list may not include all maintenance items. Inspection intervals may
vary depending on climate and opening hours. Consult your local dealer about
a service contact for seasonal inspections.
b
Monthly maintenance items and outdoor unit rinsing may be performed by the
customer. All other maintenance items and all service work must be performed
by a qualified service technician. Read all warning labels.
c
Do not use harsh chemicals or high pressure water on coils. More frequent rins-
ing is required near a sea coast.
Specifications subject to change without notice.
MAINTENANCE CHECKLIST
c
MAINTENANCE CHECKLIST
c
RECOMMENDED
a
INTERVAL
b
Monthly
Annual
X
X
X
X
X
X
X
d
X
RECOMMENDED
a
INTERVAL
b
Monthly
Annual
X
X
X
X
X
X
X
X
FASFHS150-180-01SI