Condensate Drain - Carrier FAS150 Installation, Start-Up And Service Instructions Manual

Packaged air-handling units with r-410a refrigerant 60 hz
Table of Contents

Advertisement

A
A
First On/Last Off = B
Vertical Installation
First On/Last Off = A
Horizontal Installation
Fig. 8 — Typical Evaporator Coil Connections
(FAS/FHS)
Vapor Line
Vapor Line
45°
45°
LEGEND
TXV — Thermostatic Expansion Valve
NOTE: The 8 o'clock position is shown above.
Fig. 9 — TXV Sensing Bulb Location
14
Liquid Line
Liquid Line
Connection
Connection
B
B
Suction-Vapor
Suction-Vapor
Connection
Connection
Condensate
Condensate
Drain
Drain
Connection
Connection
B
B
A
A
Condensate Drain Connection
Strap
Strap
TVX Bulb
TVX Bulb
Specifications subject to change without notice.

Condensate Drain

Install a trapped condensate drain line to unit connection as
shown in Fig. 10. The unit drain connection is a PVC stub.
(See Fig. 11.) Some areas may require an adapter to con-
nect to either galvanized steel or copper pipe. For these ap-
plications, install a field-supplied threaded PVC adapter.
NOTE: A trap must be installed in the condensate drain line
to ensure that the static pressure of fans is balanced with
the water column in the drain line and that condensate can
drain completely from pan. Without a trap, air can be drawn
up drain line until water level in condensate pan becomes
equal to static pressure created by fans, preventing com-
plete drainage. Conditions will worsen as filters become
dirty.
Install clean-out plugs in trap. Pitch drain line downward to
an open floor drain or sump. Provide service clearance
around drain line to permit removal of unit panels. Observe
all local sanitary codes.
As shipped, the unit's condensate drain pan is NOT sloped
towards the drain connection. The pan slope must be
changed to pitch towards the side of the unit with the drain
connection. (See Fig. 11.) Loosen the 2 screws next to the
drain outlet at both ends of the unit, push drain pan down in
the slots near the drain connection, and up in the slots on
the opposite end. Re-tighten screws. The pan should have
a pitch of at least 1/4 in. over its length toward the drain
connection.
Plug
Plug
Plug
Plug
3" Min.
3" Min.
[76]
[76]
Plug
Plug
Existing Floor
Existing Floor
Drain, Sink, or
Drain, Sink, or
Hopper
Hopper
1" Min.
1" Min.
[25]
[25]
To Sewer
To Sewer
NOTE: Dimensions in [ ] are in millimeters
Fig. 10 — Condensate Drain
From
From
Condensate
Condensate
Pan
Pan
3" Min.
3" Min.
3" MIN.
[76]
[76]
[76]
Plug
Plug
Unit
Unit
Condensate
Condensate
Conn
Conn
3" Min.
3" Min.
[76]
[76]
Trap
Trap
Not Less Than 18" [457]
Not Less Than 18" [457]
Long and Two Sizes
Long and Two Sizes
Larger Than Waste Pipe
Larger Than Waste Pipe
Trap
Trap
FASFHS150-180-01SI

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fas180Fas240Fhs180Fhs240

Table of Contents