3

System overview

3.1

Front panel

Number Symbol
Bosch Security Systems, B.V.
Element
1
Zone status
indicator light
2
Combined fault
warning indicator
light
3
Recessed button
Description
Indicates the status of the zone:
Green = Zone is in use for non-emergency
purpose
Yellow = Zone fault detected (Note: The
indication of this status has the highest
priority)
Red = Zone is in use for emergency purpose
Off = Zone in idle condition
This indicator lights up yellow if a fault in the
device is detected.
Note: The fault types to be indicated via this
indicator can be configured.
The button is protected to prevent it from being
pressed accidentally. Use a pointed object (such
as a ballpoint pen) to press the button.
This button has the following functions if the CAN
address of the device is not set to 00:
Find function: If the find function of the
device is activated, press this button to
deactivate the indicators.
Displaying the CAN baud rate: Press this
button for at least one second. Please refer to
section Displaying the CAN baud rate, page
23 .
LED test: Press this button for at least three
seconds to activate the LED test. All
indicators at the front panel light up as long
as the button is pressed.
This button has the following functions if the CAN
address of the device is set to 00:
Resetting a fault (e.g. watchdog fault): Press
the button briefly to confirm a fault.