PAVIRO Router
Figure 6.3: Using supervised or isolated inputs of the CONTROL IN port
Supervised control inputs
The supervised control inputs can be used as
When using a supervised input (e.g. for connecting a CIE) add two resistors as illustrated
above (if not already included in the outputs of the connected device).
Notice!
i
The supervised inputs are internally equipped with 8.2 kΩ pull up resistors. The ground pins
are equipped with a common self resettable 140 mA fuse.
Isolated control inputs
The isolated control inputs can be used as normal logical (high/low) input (with low <= 5 V or
high >= 10 V) only. This inputs comply with VDE 0833-4.
6.6

Control output

Bosch Security Systems, B.V.
normal logical (high/low) input (with low <= 5 V or high >= 10 V) or
supervised input with states active, not active, open circuit or short circuit.
User manual
Connection | en
19