Midea V8 Series Manual page 98

Hide thumbs Also See for V8 Series:
Table of Contents

Advertisement

V8 Mini R410A VRF 50Hz
4.7 Direction of refrigerant pipe connection
Field piping can be connected in 4 directions. Before connecting, knock off the plate in the corresponding direction.
Figure 3-4.9: Direction of refrigerant pipe connection
Front out
pipe
Figure 3-4.10: The connection method of the forward outlet pipe
Gas side piping
(provided on site)
Liquid side piping
(provided on site)
Figure 3-4.12: The connection method of the downward outlet pipe.
Liquid side piping
(provided on site)
4.8 Pipe Flushing
4.8.1 Purpose
To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the
system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 4.1.1 "Installation procedure",
pipe flushing should be performed once the piping connections have been completed with the exception of the final
connections to the indoor units. That is, flushing should be performed once the outdoor units have been connected but
before the indoor units are connected.
96
Back out
pipe
Side out
pipe
Bottom out
pipe
Liquid side
stop valve
Gas side
stop valve
Gas side piping
(provided on site)
Figure 3-4.11: The connection method of the rightward outlet pipe.
Figure 3-4.13: The connection method of the backward outlet pipe.
Gas side piping
(provided on site)
Liquid side piping
(provided on site)