2.2 Indoor Units
2.2.1 Placement considerations
Placement of indoor units should take account of the following considerations:
 Sufficient space for drain piping and for access during servicing and maintenance should be allowed.
 To ensure a good cooling/heating effect, short-circuit ventilation (where outlet air returns quickly to a unit's air inlet)
should be avoided.
 To prevent excessive noise or vibration during operation, suspension rods or other weight-bearing fixings should
typically be able to bear twice the unit's weight.
Notes for installers
 Before installing an indoor unit, check that the model to be installed is as specified in the construction drawings
and confirm the correct orientation of the unit.
 Ensure that units are installed at the correct height.
 To allow smooth condensate drainage and to ensure unit stability (to prevent excessive noise or vibration), ensure
that units are level to within 1° of the horizontal. If a unit is not level to within 1° of the horizontal, water leakage
or abnormal vibration/noise may occur.