- Software requirements: Mini USB Cable connected to the VFD and the computer that will be doing
the programming.
By default from Hitachi, the AA101 and AA111 parameters are setup correctly:
Parameter
AA101
AA111
bA-61
bA-63
HITACHI P1 Parameters
Set up the motor parameters 
Find your motor nameplate and enter in the parameters based on the table below.
If you cannot locate the motor's base frequency, the name plate should tell you how many poles
there are on the motor. You can also call the motor manufacturer to figure out the number of poles.
Using the motor's maximum RPM and its number of poles, you can calculate the base frequency
with the formula below:
Base Frequency = Rated RPM * Number of Poles / 120
Max Frequency = Max RPM * Number of Poles / 120
 Parameters
AC120
AC122
Hb102
Description
Main Speed Source_M
Run-cmd. Source_M1
Enable Braking Resistor
Brake Resistor Resistance
(Ohms)
Description
Motor Accel. Time
Motor Decel. Time
Motor Rated KWs
Default Value
1 (Term.[Ai1])
0 (Term.[FW]/[RV])
0
10
Default
4 Seconds
3 Seconds
1.5 kW
Desired Value
1
0
2
Applicable resistor value
Range
0.0 to 3600.0 Seconds
0.0 to 3600.0 Seconds
0.00 to 650.00 kW