Haier GE NF80XV Series Service Manual page 8

80% two stage variable speed ultra low nox gas furnace
Table of Contents

Advertisement

second stage prove switch closes during the first stage
heat pre-purge, the control will allow second stage heat.
Once the first stage prove switch is determined to be open,
the combustion air inducer is energized on low (first stage)
heat speed. When the differential in the prove switch is
great enough, the prove switch closes and a 15-second
pre-purge begins.
NOTE: During abnormal conditions such as low supply
voltage or low outdoor temperatures and the low fire
pressure switch does not close, the combustion air inducer
will switch to high fire. After a 15 second pre-purge the
high fire pressure switch will close and the unit will begin
operation on high fire. After 10 to 20 seconds of high fire
operation the unit will switch to low fire.
After the 15-second pre-purge period, the SureLight
warms up for 20 seconds after which the gas valve opens
for a 4-second trial for ignition. The ignitor energizes during
the trial until flame is sensed. If ignition is not proved during
the 4-second period, the control will try four more times
with an inter purge and warm-up time between trials of 35
seconds. After a total of five trials for ignition (including
the initial trial), the control goes into Watchguard-Flame
Failure mode. After a 60-minute reset period, the control
will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be positioned
for the particular application. DIP switch 1, labeled T"STAT
HEAT STAGE is factory-set in the OFF position for use
with a two-stage thermostat. Move the DIP switch to ON
for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners will
always fire on first-stage heat. The combustion air inducer
will operate on low speed and indoor blower will operate on
low heat speed. The unit will switch to second stage heat
after a "recognition period". DIP switch 2, labeled SECOND
STAGE DELAY, is factory set in the OFF position for a 7
minute recognition period. The switch can be moved to the
ON position for a 12 minute recognition period, after which
time the unit will switch to secondstage heat.
While in the two-stage thermostat mode (two DIP switch
setting) the burners will fire on first-stage heat. The
combustion air inducer will operate on low speed and
indoor blower will operate on low heat speed. The unit
will switch to second-stage heat on call from the indoor
thermostat. If there is a simultaneous call for first and
second stage heat, the unit will fire an first stage heat and
switch to second stage heat after 30 seconds of operation.
See Sequence of Operation flow charts in the back of this
manual for more detail.
PIN#
Table 1. SureLight
PIN#
ignitor
®
Table 2. SureLight
PIN#
Table 3. SureLight
Page 8
1
Combustion Air Inducer High
2
Combustion Air Inducer Low
3
4
Combustuion Air Inducer Neutral
5
Ignitor Neutral
Control 5 Pin Terminal
®
Designation
1
Gas Valve High Fire
2
Second Stage Prove Switch
3
4
5
6
Primary Limit In
7
Gas Valve Low Stage
8
Gas Valve Common
9
24V Neutral
10
11
Rollout Switch Out
12
1st Stage Prove Switch
Control 12 Pin Terminal
®
Designation
1
Data Input From Motor
2
3
4
Data Output To Motor
5
5 Volt Bias Supply
6
Control 6 Pin Terminal
®
Designation
Function
Ignitor
Speed
Speed
Function
Rollout In
Ground
24V Hot
Ground
Function
Common
Not Used
Not Used
31-5000734 Rev. 0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ge nf80x060v3aGe nf80x080v4bGe nf80x100v5c

Table of Contents