When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged
if subjected to more than 0.5 psig (14" W.C.). See Figure
17. If the pressure is greater than 0.5psig (14"W.C.), use
the manual shut-off valve before pressure testing to isolate
furnace from gas supply.
MANUAL MAIN
SHUT-OFF VALVE
WILL NOT HOLD
NORMAL TEST
PRESSURE
1/8 NPT PLUG
CAP
Figure 17.
When checking piping connections for gas leaks, use
preferred means. Kitchen detergents can cause harmful
corrosion on various metals used in gas piping. Use of a
specialty Gas Leak Detector is strongly recommended. It
is available under part number 31B2001. See Corp. 8411-
L10, for further details.
Do not use matches, candles, flame or any other
source of ignition to check for gas leaks.
Testing Gas Supply Pressure
A port on the inlet side of the gas valve provides access to
the supply pressure tap. See Figure 16. Loosen the screw
and connect a manometer to measure supply pressure.
The minimum supply line is 4.5" w.c. And the maximum
supply line is 13.0" w.c. Tighten screw after measurements
have been taken.
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of gas
pressure to the manometer.
31-5000734 Rev. 0
ISOLATE
GAS VALVE
FURNACE
Unit
060
080
100
060
080
100
Table 17. Supply Line and Manifold Pressure
(inches w.c.)
Page 29
Rate Check
Manifold Pressure Measurement
To correctly measure manifold pressure, follow the steps
below:
1. Remove the threaded plug from the outlet side of the
gas valve and install a field-provided barbed fitting.
Connect measuring device "+" connection to barbed
fitting to measure manifold pressure.
2.
Start unit on low heat and allow 15 minutes for unit to
reach steady state.
3.
After allowing unit to stabilize for 15 minutes, record
manifold pressure and compare to value given in
Table 17.
4.
Repeat on high heat.
5.
Shut unit off and remove manometer as soon as an
accurate reading has been obtained. Take care to
remove barbed fitting and replace threaded plug.
6.
Start unit and perform leak check. Seal leaks if found.
Proper Combustion
Furnace should operate minimum 15 minutes with correct
gas flow rate before checking combustion. Take combustion
sample beyond the flue outlet. Table 16 shows acceptable
combustion for ALL NF80XV models. The maximum
carbon monoxide reading should not exceed 100 ppm.
Firing Rate
High Fire
Low Fire
Natural
HIgh Fire
in. w.c.
3.0 - 3.8
2.5 - 3.3
CO
% for Nat
2
6.0 - 7.5
Table 16.
Low Fire
in. w.c.
1.3 - 1.7
1.3 - 1.7