9 SPRING CLAMP TERMINAL BLOCK
9 - 4
POINT
• If the stripped wire is inserted into the corresponding hole without installing the
bar solderless terminal, the connection check indicator does not come out. Do
not use the stripped wire without installing the bar solderless terminal.
• The wire strip length must follow the specification of the bar solderless terminal.
Also, use a crimp tool when installing the bar solderless terminal to the wire.
• Before inserting the bar solderless terminal, check the corresponding circular
shaped hole and the bar solderless terminal. Before inserting, pay attention to
the angle of bar solderless terminal.
If a bar solderless terminal, which is bigger than the insertion slot, is inserted,
the terminal block may be damaged.
Insertion Slot Shape
2.2mm (0.09inch)
2.85mm
(0.11inch)
(3) Cable Removable
Insert the tool into the corresponding square shaped hole until it stops.
Pull the wire out of the hole completely.
MELSEC-Q
9 - 4