4.2 Interface data

RS232C
Driver load
Voltage transmit (at 3kΩ)
Voltage receive
RS485
Driver load
Signal voltage TX
Addressing
Max. cable length
Repeater
Current M-Bus IN
Capacity
Galvanic isolation
USB
Type
USB IC
Power supply
Max. cable length
Ethernet
Network interface
Protocols / adressing

4.3 Ordering information

Article number
PW100
NT016
KA USB AB
KA PATCH.5E RJ45 1M
KA006
PW100 · User Manual Version 1.0 - 11/2020
Current max. 5mA, resistive: min. 3kΩ, capacity: max. 2,5 nF
Mark: +5V ≤ U
Space: -15V ≤ U
Mark: +2,5V ≤ U
Space: -15V ≤ U
Current max. 250 mA, resistance min. 54Ω
Space (0): +1.5V  U
Mark (1): -5.0V  U
Not possible (transparent)
3,0 m
Basic current < 1,5 mA (1 Unit Load), TX current typ. 15mA
Max. 250 pF
> 2,5 kV to all interfaces, M-Bus and power supply
USB 2.0 device, socket type B
FTDI Chip: FT232R, Vendor ID = 0403, Product ID = 6001
Bus powered, Low Power (max. 90mA)
3,0 m
10/100BaseT (RJ45), auto-MDIX, with 2 LEDs
TCP and UDP / static IP or dynamic IP (DHCP)
Description
M-Bus Level Converter and Repeater for 100 slaves
Power supply 42VDC, 30W, rail, input range 85 .. 264 VAC, 47 .. 63 Hz
USB cable A to B plug/plug, length = 1m, grey
Network patch cable CAT5E FTP, Length = 1m, grey
Serial D-SUB-9 female cable with 3 open wires
≤ +15V
T
≤ -5V
T
≤ +15V
R
≤ -2,5V
R
 +5.0V
t
 -1.5V
t
PW100
16