3.6 Ethernet interface

The Ethernet interface of the PW100 converts the physical interface Ethernet 10/100BaseT to M-Bus and the
TCP / IP protocol to the serial protocol. The Ethernet interface is available in the front panel as an 8-pin RJ45
socket. The PW100 can be integrated into an existing local network and the M-Bus meters can be read from
one or more PCs in that network. This requires the so-called "Tibbo Device Server Toolkit" to be installed on
that PC. With this software the Ethernet interface is configured in the PW100 and a virtual COM port is set up.
This simulated serial interface enables the use of the usual M-Bus software designed for normal serial inter-
faces. Please perform the following steps of installation:
3.6.1 IT preparations
The IT division of the network containing the PW100 must define the following items:
Fixed IP address must be identical to the IP range of the reading computer. Only the last number must
be different. (e.g. 192.168.1.239)
You need also the subnet mask and IP address of the gateway if the IP addresses are reassigned by a
gateway.
The converter uses the port 1001 by default for the TCP protocol. This port must not be blocked by any
firewall.
You can find your own IP address in your network this way:
PW100 · User Manual Version 1.0 - 11/2020
PW100
Start – Run: cmd <OK>