Download Print this page
Emerson Coils ESC Series Operating Instructions Manual
Emerson Coils ESC Series Operating Instructions Manual

Emerson Coils ESC Series Operating Instructions Manual

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

Quick Links

G e n e r a l i n f o r m a t i o n :
ESC Series Coils are for use with certain EMERSON products.
Coil
Voltage
±10%
ESC-24VAC
24VAC
(17VA)
ESC-230VAC
±10%
230VAC
ESC-120VAC
±10%
120VAC
ESC-24VDC
±10%
24VDC
(17VA)
ESC-W24VAC
±10%
24VAC
(38VA)
ESC-W230VAC 230VAC
±10%
Note: MOPD will decrease if the coils will be used at 60Hz frequency. Also follow the operating instructions of the used devices.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to comply can result in device
failure, system damage or personal injury.
• According to EN 13313 it is intended for use by persons having the
appropriate knowledge and skill.
• Do not exceed the specified maximum ratings for pressure, temperature,
voltage and current.
• The coil should be fused in accordance with local codes. Electrically ground
the valve body.
• Ensure that the system piping is grounded.
• Before installation or service disconnect all voltages from system and device.
• Do not energize coil unless it is attached to the device.
• Observe and avoid mechanical damage of component housing.
• Ensure that design, installation and operation are according to European and
national standards/regulations.
I n s t a l l a t i o n o f C o i l s : ( F i g . 1 a , 1 b , 1 c )
• Mount O-ring with smaller diameter (1) over enclosing tube.
• Place coil over the enclosing tube and press it down by hand.
• Place the black retainer (2) on the upper visible end of the enclosing tube. The two
slots of the retainer fit to stumps of ESC coil. (5)
• Insert O-ring with larger diameter (3) inside of the orange screw cap
• Press coil well down and tight the screw cap (4) over the retainer first hand tight
and then with torque 0.5-0.6 Nm in order to provide IP65 protection. Use spanner
size 27mm.
E l e c t r i c a l c o n n e c t i o n :
• Entire electrical connections have to comply with local regulations.
• Before energizing the device, be sure that the source voltage and frequency
matches that on the coil label.
• Standard plug and cable assembly (ASC-N...)
Brown and blue color wires (BN & BL Fig. 2) to be connected to the power supply
and yellow/green color wire to the ground. Connect pre-wired plug to the coil and
tighten screw with 0.2 Nm.
• Plug and cable with electronic chopper module (DS2-N15)
Polarity protected two wires to be connected to the power supply.
• Wiring with DIN Plug (Fig. 3)
Cable with three wires has to be connected to terminal 1 and 2 and
the plug terminal box. Connect pre-wired DIN-plug to the coil and tighten screw
with 0.2 Nm.
Emerson Climate Technologies GmbH
Am Borsigturm 31 I 13507 Berlin I Germany
Approved
Frequency
50(60) Hz
50(60) Hz
(17VA)
50(60) Hz
(17VA)
--
50(60) Hz
(38VA)
50(60) Hz
www.climate.emerson.com/en-gb
Operating instructions
Coils ESC Series
Expansion Valves
EX2
Markings
,
S e r v i c e / M a i n t e n a n c e :
!
Warning:
• ESC coils are intended for continuous-duty, which when energized for an
extended period of time, it becomes hot. This is normal. Do not touch the coil
during operation. Wait for coil temperature to cool down before attempting
to dissemble it, or use gloves, failure to do so could lead to injury.
• Disconnect electrical power before service.
• Dismantle of ESC: unscrew the screw cap (4) and pull the coil with retainer (2)
out. Remove smaller O-ring.
• Replacement of ASC.../ ASC3... with ESC series:
- Dismantle ASC... by opening blue clip (Fig.4)
- Dismantle ASC3...: see Fig. 5. Remove smaller O-ring.
- To ensure proper function and protection, only O-rings approved for ESC coils
may be used. Any existing O-rings must be replaced.
T e c h n i c a l D a t a :
Coil
ESC 24V
ESC 230V
ESC 120V
ESC 24VDC
ESC-W24VAC
ESC-W230VAC
Supply voltage variation
Ambient temperature range
Protection class
Vibration resistance
(ground) on
Date: 23.07.2019
Devices
Solenoid Valves
110RB,
240RA,
CX2
200RH
200RB
540RA
Inrush current
with EMERSON offered Cables and plugs)
Oil management
M36
OM3/4
OM5
Holding current
(A)
(A)
2.23
0.57
0.22
0.052
0.48
0.11
-
0.72
2.7
1.2
0.52
0.11
±10%
-40...+60°C
IP65
(properly installed on enclosing tube
0.7g 10 ... 200 Hz
ESC_OI_ML_866915_R02.docx

Advertisement

loading

Summary of Contents for Emerson Coils ESC Series

  • Page 1 Operating instructions Coils ESC Series G e n e r a l i n f o r m a t i o n : ESC Series Coils are for use with certain EMERSON products. Devices Expansion Valves Solenoid Valves Oil management...
  • Page 2 Betriebsanleitung Spulen Baureihe ESC B e s c h r e i b u n g : ESC Spulen sind für die Verwendung mit verschiedenen EMERSON Produkten vorgesehen. Geräte Expansionsventile Magnetventile Ölreguliersystem zugelassene 110RB, 240RA, 200RH OM3/4 Spule Spannung Frequenz...
  • Page 3 Bobines Série ESC I n f o r m a t i o n s g é n é r a l e s : Les bobines de la série ESC sont destinées à être utilisées avec certains produits EMERSON. Appareil Régulateur de...
  • Page 4 Instrucciones de funcionamiento Bobinas de la serie ESC I n f o r m a c i ó n g e n e r a l : Las bobinas de la serie ESC son válidas para ciertos productos EMERSON. Componente Sistema de Válvula de...
  • Page 5 Istruzioni operative Bobine Serie ESC I n f o r m a z i o n i g e n e r a l i : Le bobine serie ESC possono essere utilizzate per i prodotti vari EMERSON. Dispositivo Valvole di...
  • Page 6 Руководство по эксплуатации Катушки ESC О б щ а я и н ф о р м а ц и я : Катушки серии ESC предназначены для определённых продуктов EMERSON. Устройство Электронные Pасширительный Соленоидные вентили регуляторы клапан уровня масла Разрешённа 110RB,...
  • Page 7 Fig./ Pис. 1a: Fig./ Pис. 1c: Fig./ Pис. 1b: Fig./ Pис. 2 ASC-N… Fig./ Pис. 3 DIN-Plug Fig./ Pис. 4 ASC- … Fig./ Pис. 5: ASC3-W… Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Am Borsigturm 31 I 13507 Berlin I Germany Date: 23.07.2019 ESC_OI_ML_866915_R02.docx...

This manual is also suitable for:

Esc-24vacEsc-230vacEsc-120 vacEsc-24vdcEsc-w24vacEsc-w230vac