Grundfos UPM3 Installation And Operating Instructions Manual page 10

Hide thumbs Also See for UPM3:
Table of Contents

Advertisement

Contact
PWM
1
PWM input
2
Signal reference
3
PWM output
1 x 230 V - 15 % /+ 10 %
50/60 Hz
L
PE
N
Control box without signal connection
PWM
SYSTEM
CONTROLLER
1 x 230 V - 15 % /+ 10 %
50/60 Hz
IN
REF
L
OUT
PE
N
Control box with Mini SS connection
5.4.1 Power supply connection
The pump must be connected to the power supply with the TE
Superseal connector.
Adapters are available for cables with Molex or Volex connectors.
10
LIN
Cable
VBAT
Brown
Signal reference
Blue
LIN bus signal
Black
5.4.2 Control signal connection
Connect the signal wires to the correct poles. Otherwise,
the pump may be damaged.
UPM3 pumps are externally speed-controlled. A signal cable is
required to enable the pump control. Otherwise, the pump with
profile A runs continuously at maximum speed, while the pump with
profile C stops.
UPM3 HYBRID pumps are either internally or externally speed-
controlled.
If you set the pump to external control mode (PWM A or C profile)
via the operating panel, you need a signal cable. If you set the
pump to internal control mode, a blind plug can be used to close the
signal connection.
The signal cable connection has three leads: signal input, signal
output and signal reference. The cable must be connected to the
control box by either a FCI or TE Mini Superseal connector.
The cable length can be customised to specific requirements (max.
3 m).