44 Parameters
No.
Name/Value/Range

114 Extension I/O module 1

114.01
Option module 1 type
None
FIO-01
FIO-11
114.03
Option module 1 status
No option
No communication
Unknown
FIO-01
FIO-11
114.05
DIO status
114.09
DIO1 configuration
Output
Input
114.11
DIO1 output source
Off
Always On
Fault
No fault
Grid connected
Grid not connected
Power level 20%
Power level 40%
Description
Activates and specifies the type of I/O extension
module 1.
None
FIO-01
FIO-11
Displays the status of I/O extension module 1.
No module detected in the specified slot.
A module has been detected but cannot be
communicated with.
The module type is unknown.
An FIO-01 module has been detected and is
active.
An FIO-11 module has been detected and is
active.
(Visible ony when parameter
module 1 type
is FIO-01 or FIO-11.)
Displays the status of the digital input/outputs on
the extension module. The activation/
deactivation delays (if any are specified) are
ignored. Bit 0 indicates the status of DIO1.
Note: The number of active bits in this parameter
depends on the number of digital input/outputs on
the extension module.
Example: 00001001b = DIO1 and DIO4 are on,
remainder are off.
This parameter is read-only.
(Visible only when parameter
module 1 type
is FIO-01 or FIO-11.)
Selects whether DIO1 of the extension module is
used as a digital input or output.
DIO1 is used as a digital output.
DIO1 is used as a digital input.
(Visible only when parameter
module 1 type
is FIO-01 or FIO-11.)
Selects an inverter signal to be connected to
digital input/output DIO1 of the extension module
when parameter
114.09 DIO1 configuration
to Output.
Relay output activation when fault.
Relay output activation when no fault.
Relay output activation when grid connected.
Relay output activation when grid not connected.
Relay output activation when output power level
over 20% of rated power.
Relay output activation when output power level
over 40% of rated power.
Default
FbEq (16b/32b)
None
0
1
2
No option
0
1
2
15
20
114.01 Option
-
1 = 1
114.01 Option
Input
0
1
114.01 Option
Off
is set
0
1
2
3
4
5
6
7