Activated Conditions Of Hba; Remarks - Taie FA Series Operation Manual

Digital pid temperature/process controllers
Hide thumbs Also See for FA Series:
Table of Contents

Advertisement

12.5

Activated conditions of HBA

Condition
1. OUT1 is ON
2. Heater current is less the HBA set value
3. Condition1 and 2 continued more than 5 seconds
AL1 will be activated, if condition 1&2&3 are all "true".
12.6

Remarks

Available output(OUT1) type for HBA
I.
Relay
II.
Voltage pulse (SSR drive)
Since HBA function uses AL1 as alarm relay, please set temperature alarms in AL2 or
AL3.