Transformer protection RET650
Version 2.2
Table 45. Two step overvoltage protection OV2PTOV
Function
Operate voltage, step 1 and 2
Reset ratio
Absolute hysteresis
Inverse time characteristics for steps 1 and
2, see table
151
Definite time delay, low step (step 1) at 0 to
1.2 x U
set
Definite time delay, high step (step 2) at 0
to 1.2 x U
set
Minimum operate time, Inverse
characteristics
Operate time, start function
Reset time, start function
Operate time, start at 0 to 2 x U
Reset time, start at 2 x U
to 0
set
Operate time, start at 0 to 1.2 x U
Reset time, start at 1.2 x U
set
Critical impulse time
Impulse margin time
64
Range or value
(1.0-200.0)% of UBase
>98%
(0.0–50.0)% of UBase
-
(0.00 - 6000.00) s
(0.000-60.000) s
(0.000-60.000) s
25 ms typically at 0 to 2 x U
30 ms typically at 0 to 1.2 x 30
ms typically at 0 to 2 x U
25 ms typically at 0 to 2 x U
20 ms typically at 1.2 x 40 ms
typically at 2 x U
Min. = 15 ms
set
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 20 ms
set
Max. = 35 ms
to 0
Min. = 5 ms
Max. = 25 ms
10 ms typically at 0 to 2 x U
15 ms typically
© 2017 - 2021 Hitachi Power Grids. All rights reserved
M13304-1 v15
Accuracy
±0.5% of U
at U ≤ U
r
±0.5% of U at U > U
-
±0.5% of U
at U ≤ U
r
±0.5% of U at U > U
See table
151
±0.2% or ±45 ms whichever is greater ±0.5% ±25
±0.2% or ±45 ms whichever is greater ±0.5% ±25 ms
±0.2% or ±45 ms whichever is greater ±0.5% ±25 ms
-
set
set
-
set
to 0
set
-
-
-
-
-
set
-
1MRK 504 172-BEN G
r
r
r
r
Hitachi Power Grids