Transformer protection RET650
Version 2.2
Table 151. Inverse time characteristics for overvoltage protection
Function
Type A curve:
k
=
t
æ
ö
-
>
U
U
ç
÷
è
ø
>
U
EQUATION1436-SMALL V1 EN-US
U> = U
set
U = U
measured
Type B curve:
k
480
t
2.0
U U
n
32
0.5
U
n
IECEQUATION2423 V2 EN-US
Type C curve:
×
k
480
=
t
3.0
-
>
æ
ö
U U
n
×
-
32
0.5
ç
÷
>
è
U
ø
IECEQUATION2421 V1 EN-US
Programmable curve:
×
k A
=
+
t
P
æ
ö
-
>
U
U
ç
÷
×
-
B
C
è
ø
>
U
EQUATION1439-SMALL V1 EN-US
Hitachi Power Grids
Range or value
k = (0.05-1.10) in steps of 0.01
k = (0.05-1.10) in steps of 0.01
0.035
k = (0.05-1.10) in steps of 0.01
+
0.035
k = (0.05-1.10) in steps of 0.01
A = (0.005-200.000) in steps of 0.001
B = (0.50-100.00) in steps of 0.01
D
C = (0.0-1.0) in steps of 0.1
D = (0.000-60.000) in steps of 0.001
P = (0.000-3.000) in steps of 0.001
© 2017 - 2021 Hitachi Power Grids. All rights reserved
SEMOD116978-2 v11
1MRK 504 172-BEN G
Accuracy
±5% +60 ms