GE AF-600 FP Design Manual page 99

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

AF-600 FP Design Guide
Set Preset reference 0 to first preset speed (par. C-05 Multi-step Frequency 1 - 8 [0]) in percentage of Max reference speed (par. F-53 Maximum Reference). Ex.:
60%
Set preset reference 1 to second preset speed (par. C-05 Multi-step Frequency 1 - 8 [1] Ex.: 0 % (zero).
Set the timer 0 for constant running speed in par. LC-20 Logic Controller Timer [0]. Ex.: 2 sec.
Set Event 1 in par. LC-51 Logic Controller Event [1] to True [1]
Set Event 2 in par. LC-51 Logic Controller Event [2] to On Reference [4]
Set Event 3 in par. LC-51 Logic Controller Event [3] to Time Out 0 [30]
Set Event 4 in par. LC-51 Logic Controller Event [4] to False [0]
Set Action 1 in par. LC-52 Logic Controller Action [1] to Select preset 0 [10]
Set Action 2 in par. LC-52 Logic Controller Action [2] to Start Timer 0 [29]
Set Action 3 in par. LC-52 Logic Controller Action [3] to Select preset 1 [11]
Set Action 4 in par. LC-52 Logic Controller Action [4] to No Action [1]
5
Set the Logic Controller in par. LC-00 Logic Controller Mode to ON.
Start / stop command is applied on terminal 18. If stop signal is applied the frequency converter will decel and go into free mode.
98