5.1.13 Cascade Controller Wiring Diagram
The wiring diagram shows an example with the built in BASIC Cascade Controller with one variable speed pump (lead) and two fixed speed pumps, a 4-20 mA
transmitter and System Safety Interlock.
5.1.14 Start/Stop Conditions
Commands assigned to digital inputs. See Digital Inputs, parameter group ID-40.
Start (SYSTEM START /STOP)
Lead Pump Start
Coast (EMERGENCY STOP)
Safety Interlock
Function of buttons on keypad:
Hand
Off
Auto
Variable speed pump (lead)
Accels (if stopped and there is a demand)
Accels if SYSTEM START is active
Coast to stop
Coast to stop
Variable speed pump (lead)
Accels (if stopped by a normal stop command) or
stays in operation if already running
Decels
Starts and stops according to commands via ter-
minals or serial bus
AF-600 FP Design Guide
Fixed speed pumps
Staging (if stopped and there is a demand)
Not affected
Cut out (built in relays are de-energized)
Cut out (built in relays are de-energized)
Fixed speed pumps
Destaging (if running)
Decels
Staging/Destaging