GE AF-600 FP Design Manual page 66

Fan and pump drive
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Illustration 4.6: Recommended lifting method, Unit Size 63
(460V, 600 to 900 HP, 575/600V, 900 to 1150 HP).
NB!
Note the plinth is provided in the same packaging as the frequency converter but is not attached to Unit Sizes 61-64 during shipment. The plinth is required to
allow airflow to the drive to provide proper cooling. The Unit Sizes6 should be positioned on top of the plinth in the final installation location. The angle from the
top of the drive to the lifting cable should be 60 degrees or greater.
4.1.6 Safety Requirements of Mechanical Installation
Pay attention to the requirements that apply to integration and field mounting kit. Observe the information in the list to avoid serious injury or
equipment damage, especially when installing large units.
The frequency converter is cooled by means of air circulation.
To protect the unit from overheating, it must be ensured that the ambient temperature does not exceed the maximum temperature stated for the frequency
converter and that the 24-hour average temperature is not exceeded. Locate the maximum temperature and 24-hour average in the paragraph Derating for
Ambient Temperature.
If the ambient temperature is in the range of 45 °C - 55 ° C, derating of the frequency converter will become relevant, see Derating for Ambient Temperature.
The service life of the frequency converter is reduced if derating for ambient temperature is not taken into account.
4.1.7 Field Mounting
For field mounting the IP 21/IP 4X top/TYPE 1 kits or IP 54/55 units are recommended.
Illustration 4.7: Recommended lifting method, Unit Size 64
(460V, 1000 to 1200 HP, 575/600V, 1250 to 1350 HP).
AF-600 FP Design Guide
4
65