4.2.3 Installation Angle Requirements

Inverter vertically or at a minimum back tilt of 10°. Forward installation or upside down installation is prohibited.
Vertical

4.2.4 Installation Clearance Requirements

1) Reserve enough clearance around the inverter to ensure sufficient space for heat dissipation. (The fans are
maintained on the left side of the inverter, and a larger clearance is required.)
In case the distance is less than 800mm, move the inverter from the mounting-bracket or wall before maintaining fans.
2) In case of multiple inverters, reserve specific clearance between the inverters.
FIG 4-3 Single installation space
3) In case of back-to-back installation, reserve specific clearance between the two inverters.

4.3 Moving the Inverter

Move the inverter to the specified position before installation. The inverter can be moved manually or via a hoist.

4.3.1 Manual Transport

Step 1 Install four hand shanks into the corresponding M12 holes, which holes in the handles at side and bottom
of the inverter.
10 /41
Backward
FIG 4-2 Installation angle
≥ 600mm
≥ 500mm
FIG 4-5 Back-to-back installation
Forward
≥ 10
800mm
FIG 4-4 Multiple installation space
500mm
4 Mechanical Mounting
Upside down
800mm
400mm