Environmental Conditions; Environmental Tests - ABB UniSec Digital Operation And Maintenance Manual

Hide thumbs Also See for UniSec Digital:
Table of Contents

Advertisement

D I S T R I B U T I O N S O LU T I O N S
5.2 MDC4-M
MDC4 -Mdimensions
Dimensions
Description
MDC-M
Installation

Environmental conditions

Description
Operating temperature
range
Enviroment humidity
Atmospheric pressure
Altitude
Transport and storage
temperature range
Overvoltage category
Pollution degree
Ip grade
1) For higher altitude application, please contact ABB.
Value
Width
100 mm
Height
156 mm
Depth
33 mm
Weight
0,3 kg
Guide rail
35 mm
Value
-20...70 °C
20...85%, non-condensing
86...106 kPa
Up to 2000 m
(1)
-40...85 °C
III
2
IP 20
Power supply
Description
Value
Voltage input
12...24 VDC
Power consumption
12W max
Withstand voltage level
2 kV
(50Hz, 1 min)
Output power supply
DC 12V ±10%, 3W
Controlling capacity of
5A, 30V DC
output auxiliary contact

Environmental tests

Description
Type test value
High-
+70 °C 96 H
temperature
operation
Low-
-20 °C 96 H
temperature
operation
Steady
Test for 48 H at +40
humidity-heat
°C and 93%
humidity
Alternating
Tfora maof est for
humidity-heat
48h at a maximum
test
temperature of +55
°C
19
Reference
IEC 60068-2-2
GB/T 7261-2016
IEC 60068-2-1
GB/T 7261-2016
IEC 60068-2-78
GB/T 7261-2016
IEC 60068-2-30
GB/T 7261-2016

Advertisement