Bosch Climate 5000 Series Service Manual page 77

Ducted type (medium & high static) air conditioner / heat pump
Hide thumbs Also See for Climate 5000 Series:
Table of Contents

Advertisement

4-way Valve Check
1. Power on, use a digital tester to measure the voltage, when the unit operates
in cooling, it is 0V. When the unit operates in heating, it is about 230VAC.
If the value of the voltage is not in the range, the PCB must have problems
and need to be replaced.
Figure 98
Figure 99
Bosch Climate 5000 Series Ducted Type (Medium & High Static) Air Conditioner / Heat Pump (11.2022)
2. Turn off the power, use a digital tester to measure the resistance. The value
should be 1.8~2.5 KΩ.
Figure 100
Service Manual
| 77