Rs-485 Communication Network; Cabling Recommendations; Earth/Ground Regime; Figure 20: Rs-485 Networking - FGD FlameSpec IR3 Series User Manual

Hide thumbs Also See for FlameSpec IR3 Series:
Table of Contents

Advertisement

FlameSpec IR3 User Manual

2.10 RS-485 Communication Network

Using the RS-485 network capability of the detector and communicator software, it is possible
to connect up to 32 detectors in an addressable system with only 4 wires (2 for power and 2 for
communication). Using repeaters, the number of detectors can be much larger (32 detectors for
each repeater) up to 247 on the same 4 wires. Using the RS-485 network, it is possible to read
each detector's status (fault, alarm) and to initiate a BIT to each detector individually.
The detector communicates via RS-485 with a Modbus RTU compatible protocol. For more
details on the communication protocol, please see manual F100P0013

2.11 Cabling Recommendations

The cable used should be appropriate for the hazardous area classification and meet local,
national and company regulations.
In order to comply to EMC regulations, the cable must be shielded and the detector grounded.
The use of industrial grade, suitably armored field cable is recommended. When using HART®
communications, there are some additional considerations. In particular, low capacitance cable
should be used. Further detailed information can be found at the HART® Communication
Foundation's website www.hartcomm.org.

2.12 Earth/Ground Regime

Any earthing regime employed must avoid earth loops. The following information is provided to
assist with proper earthing of the detector
There is an earthing point on the outside of the detector enclosure for connection to
Electrical ground
For more information & technical support: (+1) 714-671-8500 · support@fg-detection.com

Figure 20: RS-485 Networking

F120V0020.07
19

Advertisement

Table of Contents
loading

Table of Contents