11.3.3
Evacuation of the Equipment
WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND
PIPES in the following procedure.
1
Connect a charging hose with a push pin to the Low side of a charging set and the service port of the 3-way
valve.
Be sure to connect the end of the charging hose with the push pin to the service port.
o
2
Connect the center hose of the charging set to a vacuum pump.
3
Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from
0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes.
4
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6
Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to "OPEN"
using a hexagonal wrench (4 mm).
8
Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
o
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step 3 above take the
following measure:
-
If the leak stops when the piping connections are tightened further, continue working from step 3.
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
11.3.4
Connect the cable to the Outdoor Unit
1
Remove the control board cover from the unit by loosening the screw.
2
Cable connection to the power supply through Isolating Devices (Disconnecting means).
Connect approved type polychloroprene sheathed power supply cord 3 × 4.0 mm
o
245 IEC 57 or heavier cord to the terminal board, and connect the other end of the cord to Isolating
Devices (Disconnecting means).
Do not use joint power supply cord. Replace the wire if the existing wire (from concealed wiring, or
o
otherwise) is too short.
In unavoidable case, joining of power supply cord between isolating devices and terminal board of air
o
conditioner shall be done by using approved socket and plug rated 25A. Wiring work to both socket and
plug must follow to national wiring standard.
3
Connection cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 ×
2
1.5 mm
flexible cord, type designation 245 IEC 57 or heavier cord. Do not use joint connection cable.
Replace the wire if the existing wire (from concealed wiring, or otherwise) is too short.
Indoor unit
OPEN
Lo
Vacuum
pump
Liquid side
Two-way valve
Close
Gas side
Three-way valve
Close
Hi
CLOSE
66
Outdoor unit
2