RH% MENU - SETTING OF HUMIDITY THRESHOLDS
Access the RH% menu to set the operating thresholds relating to humidity regulation.
Humidity regulation is active only when the temperature regulation operation is set
to air conditioning. The parameters to be set are HR1 (switch-on threshold of the
dehumidifier), HR2 (switch-off threshold of the air conditioner), HRd (intervention
differential, common for HR1 and HR2, centered on the threshold).
The condition is 20 ≤ HR1≤ HR2 ≤ 80.
When the dehumidifier is active, the RH indication is lit on the display.
The humidity and temperature regulation are linked to each other to meet the need to
contain humidity while cooling and to avoid the dew point.
In particular:
• when the measured humidity is lower than the HR1 threshold, the dehumidifier is
always off while the air conditioner is on if the measured temperature is above
the setpoint
• when the measured humidity is between HR1 and HR2, the air conditioner
and dehumidifier are switched on only when the measured temperature
is above the setpoint, otherwise they are switched off
• when the measured humidity is higher than the HR2 threshold, the dehumidifier
is switched on if the measured temperature is higher than the setpoint while
the air conditioner is always off.
How to modify the humidity thresholds
Initial screen
Ignition threshold
dehumidifier
After completing the parameter setting:
• press the key
• press the key
3s
SET
Menu configuration
Shutdown threshold
conditioner
once to return to the configuration menu
twice to exit the menu and return to the initial screen
TUO Wi-Fi RF Chronothermostat with humidistat User Manual
- 67 -
x3 times
Menu humidity
Differential for
HR1 and HR2