Installing A Multiplex Device; Adding Multiplex Devices To The Control Panel Table 7; Removing Multiplex Devices From The Control Panel; Multiplex Devices - Bosch D8125MUX Operation And Installation Manual

Multiplex bus interface
Hide thumbs Also See for D8125MUX:
Table of Contents

Advertisement

D8125MUX | Operation and Installation Guide | 3.0
3.7

Installing a Multiplex Device

As shown in Table 6, several types of multiplex
devices are available. Each multiplex accessory
device is packaged with instructions connecting to the
multiplex bus output.
Table 6:

Multiplex Devices

Product
DS7432 Eight Input Remote Module
DS7450 Flush Mount Single Multiplex
Contact Point
DS7452 Surface Mount Single Multiplex
Contact Point
DS7457 Single Multiplex Input Module
DS7460 Dual Zone Input Module
DS7465 Input/Output Module
MX775 (DS7470) Multiplex PIR Intrusion
Detector – 50 ft (15 m) Mirror
MX934 (DS7471) Multiplex PIR Intrusion
Detector – 35 ft (11 m) Mirror
MX938 (DS7472) Ceiling Mount Multiplex
PIR Intrusion Detector
MX540 (DS7473) Multiplex PIR Intrusion
Detector – 40 ft (12 m) Fresnel Lens
MX794 (DS7474) Multiplex Long Range
PIR Intrusion Detector
MX950 (DS7476) Multiplex
PIR/Microwave TriTech Intrusion Detector
MX835 (DS7477) Multiplex
PIR/Microwave TriTech Intrusion Detector
with Pet Immunity
MX250 Photoelectric Smoke or Photo with
Heat Detector and MXB2W Base
D7050/D7050TH Photoelectric or Photo
with Heat Detector and D7050-B6 Base
Lot #249 and greater
10
Installation
3.7.1
Adding Multiplex Devices to the Control
Panel
Off board points for the D9412GV2, D9412G, D9124,
D9412, and D9112 are numbered 9 through 127 and
129 through 247 (D7412GV2, D7412G, D7412, and
D7212 use off board Points 9 through 75 only;
D7212GV2 and D7212G use off board Points 9
through 40 only). The D9412GV2, D9412G, D9412,
and D9112 reserves Points 128 and 248 for internal
use. The D8125MUX connected to Zonex 1 monitors
Point Type
Points 9 through 127, whereas the D8125MUX
6
connected to Zonex 2 monitors Points 129 through
1
247.
1
2
6
3
2
3.7.2
Removing Multiplex Devices from the
Control Panel
2
To remove a multiplex device from the system:
2
1. Connect the device to the D5060.
2. Enter the address.
2
3. Enter 0 for the point type.
2
2
2
4
4
Bosch Security Systems, Inc. | 10/09 | F01U034973-02
The D8125MUX and multiplex points
connected to Zonex 2 must be
programmed in the D8125MUX with DIP
switches as Points 9 through 127. Refer
to Table 7 on page 11.
Ensure that the D8125MUX is not
powered before connecting or
disconnecting multiplex devices.
Connecting or disconnecting a multiplex
device while the D8125MUX is powered
causes the multiplex device address
setting to reprogram or scramble.
After any programming or hardware
change, do a functional test of the system
as required by local codes.