Electromagnetic compatibility of fail-safe modules

Pulse-shaped interference
The fail-safe I/O modules S7-1500/ET 200MP without external protective circuit meet the
severity level 2 for the high-energy individual pulse (surge) according to IEC 61000-4-5:2014.
Protecting S7-1500/ET 200MP against overvoltages with fail-safe modules
If your equipment requires protection from overvoltage, we recommend that you use an
external protective circuit (surge filter) between the load voltage power supply and the load
voltage input of the fail-safe modules to ensure surge immunity for the S7-1500 automation
system/ET 200MP distributed I/O system with fail-safe modules.
Note
Lightning protection measures always require a case-by-case examination of the entire
system. An almost complete protection from overvoltages, however, can only be achieved if
the entire building surroundings have been designed for overvoltage protection. In particular,
this involves structural measures in the building design phase.
If you want detailed information regarding overvoltage protection, we recommend that you
contact your Siemens representative or a company specializing in lightning protection.
You can find more information on protection from overvoltage in the Designing interference-
free controllers (http://support.automation.siemens.com/WW/view/en/59193566) function
manual.
16.4

Shipping and storage conditions

Introduction
The S7-1500 automation system / ET 200MP I/O system meet the specifications regarding
transport and storage conditions pursuant to IEC 61131-2. The following information applies
to modules that are shipped and/or stored in their original packaging.
Shipping and storage conditions for modules
Table 16- 6
Type of condition
Free fall (in shipping package)
Temperature
Barometric pressure
Relative humidity
Sinusoidal vibrations in accordance with IEC 60068-2-6
Shock in accordance with IEC 60068-2-27
Automation system
System Manual, 01/2023, A5E03461182-AK
Shipping and storage conditions
16.3 Electromagnetic compatibility of fail-safe modules
Permissible range
≤ 1 m
from -40 °C to +70 °C
From 1140 to 540 hPa (corresponds to an
altitude of -1000 to 5000 m)
5% to 95%, without condensation
5 - 9 Hz: 3.5 mm
9 - 500 Hz: 9.8 m/s
250 m/s
, 6 ms, 1000 shocks
2
Technical specifications
2
349