Maytag Goodman GM9C96 Service And Troubleshooting page 15

Two stage furnace with nine speed ecm motor
Table of Contents

Advertisement

SYSTEM OPERATION
The 2nd stage gas heat speed of the indoor blower is
energized
When the thermostat is satisfied:
The gas valve is de-energized.
The inducer remains energized for the post purge period
(15 seconds).
The indoor blower runs for the selected off delay period
(90 seconds by default, adjustable from 30 – 180
seconds).
Call for 2nd Stage Heat During 1st Stage Heat Operation
The control board receives a 24 VAC signal on the W2
terminal.
The inducer motor is enabled at high speed.
Closure of the 2nd stage pressure switch will energize
the high fire stage of the gas valve.
The 2nd stage gas heat speed of the indoor blower is
energized.
Heating Mode Speed Selection
To change the main blower speed in HEATING mode, follow
the following steps:
1. Press the left or right switch until LED displays "gA1" (for
single-stage HEATING) or "gA2" (for two-stage HEATING).
Press the center switch and LED will display the selected
speed number as Fxx (xx: Blower speed number).
2. The control will rotate available speed number every time
left / right switches are pressed. The table below shows
the available speeds for low & high heat mode.
3. Press the center switch to save the selection.
NOTE: Always refer to the Heating Chart to choose from
available heating speeds
THERMOSTAT CALL 
W/W1 
W2 
One and Two-Stage Heating Speed Table for 2 Stage IFC
Continuous Fan Mode Speed Selection
To change the main blower speed in circulation mode, follow
the following steps:
1. Press the left or right switch until LED displays "FSd".
Press the center switch and LED will display the selected
speed number as Fxx (xx: Blower speed number from 1
to 9). F03 is the default speed for circulation.
 
AVAILABLE SPEEDS 
 
F01 (DEFAULT) 
F03 
F04 
F02 (DEFAULT) 
F04 
F05 
2. The control will rotate available speed number every time
left/right switches are pressed. All 9 speeds are available
for circulation.
3. When the center switch is pressed, the current displayed
speed will be selected, and control will immediately apply
that speed setting.
THERMOSTAT 
CALL 
Circulation Speed Table for 2 Stage IFC
Cooling Mode Sequence of Operation
Low Stage Cooling Mode Sequence:
On a call for low stage cooling, the Y/Y1 or Y/Y1 and G
thermostat contacts close signaling the furnace control board
with 24 VAC on Y/Y1 or Y/Y1 and G terminals.
The 7-Segment will display the cool mode:1 A C
The compressor and condenser fan are energized.
The circulator fan is energized at low cool speed after
a cool on delay. The electronic air cleaner will also be
energized.
After the thermostat is satisfied, the compressor is de-
energized and the Cool Mode Fan Off Delay period begins.
Following the Cool Mode Fan Off Delay period, the cool
circulator and air cleaner relay are de-energized.
2nd Stage Cooling Mode Sequence:
On a call for 2nd stage cooling, the Y2 or Y2 and G thermostat
contacts close signaling the furnace control board with 24
VAC on Y2 or Y2 and G terminals.
The 7-Segment will display the cool mode: 2 A C
The compressor and condenser fan are energized.
The circulator fan is energized at cool speed after a
cool on delay. The electronic air cleaner will also be
energized.
After the thermostat is satisfied, the compressor is
de-energized and the Cool Mode Fan Off Delay period
begins.
Following the Cool Mode Fan Off Delay period, the cool
circulator and air cleaner relay are de-energized
AVAILABLE 
SPEEDS 
 
F01 
F02 
F03 (DEFAULT) 
F04 
F05 
F06 
F07 
F08 
F09 
15