7.2 MA-2000 Network Wiring Example Multiple CAN-BUS amplifier card
installed on HLSPS25 EN 54-4 PSU
max. 500 m
max. 500 m
On the CAN-BUS network, it's possible to install max. 8 of MA-BST-C cards
CanBus Netwok Cable
CBUS 218AWG:
CAN-BUS Cable 2 x 18 AWG 18 Fire Resistant PH60 EN 50200 Color Blue
Aluminium /Polyester tape 25/23 µm.
Core Type:
Flexible CI. 5-Tinned Copper
Total shield:
Drain:
Tinned copper 7 x 0,20
Can Bus Typology
Similar to all RS485 communication line, the CAN Bus is a Point-to-Point sequential connection.
The wire must have a 120 Ohm resistor at each end (on board on all boards).
The typology used is a Class A (closed Loop).
Note that it's not necessary to follow the sequential series on the peripheral's addresses.
T-taps are not permitted.
Cable must be wired in conduits separated by the mains power line and anyway wiring must be compliant to laws
and rules valid in the country of the installation.
M-167.1-MA2000-EN / 06.2022
max. 500 m
max. 500 m