Minimum Clearance To Combustible - Napoleon STARfire Series Installation And Operation Manual

Table of Contents

Advertisement

Available languages

Available languages

framing
EN
4.2
minimum clearance to combustible enclosures
WARNING
!
Risk of fire!
The front of the appliance must be finished with any non-combustible materials such as brick, marble, granite,
etc. provided that these materials do not cover the appliance opening.
important:
The HDX35 requires a minimum inside enclosure height of 70" (1778mm), measured from the bottom of the ap-
pliance. For temperature requirements, this area must be left unobstructed. It is recommended that the enclo-
sure be ventilated at the top and bottom to circulate the air.
NOTE: JOINT COMPOUNDS AND TAPES
THAT ARE RESILIENT TO HEAT AND
CRACKING SHOULD BE USED WHEN
TAPING AND MUDDING SEAMS.
MINIMUM
70"
1778mm
MINIMUM
ENCLOSURE
HEIGHT
TOP OF
FIREPLACE
OPENING
MINIMUM
28
W415-2372 / B / 12.09.20
COMBUSTIBLE
MATERIAL
37 1/4"
946mm
STEEL STUD
FRAMING
32 3/4"
SAFETY BARRIER
832mm
NON-COMBUSTIBLE
MATERIAL
TOP OF ENCLOSURE
INSULATED
SLEEVE
BRICK
2" 51mm
0" (0mm) IF NON-
COMBUSTIBLE FINISHING
IS USED SUCH AS BRICK
AND STONE
1"
25mm
52 7/16"
1332mm
MINIMUM
PLUS RISE *