ABB Relion 650 Series Product Manual page 5

Transformer protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Transformer protection RET650
Version 1.1 ANSI
110 kV Bus
200/1
20 MVA
110±11*1.5% / 21 kV
105 / 550 A
YNd5
600/1
600/1
20 kV Bus
Other configured functions
Cond
TCS SCBR
Cond
Cond
TCS SCBR
SPVN ZBAT
ANSI11000134 V1 EN-US
Figure 2.
A typical protection application for a two-winding transformer in single breaker arrangement
ABB Power Grids
50BF 3I> BF
CC RBRF
84
TCM YLTC
W1
200/1
W2
50BF 3I> BF
CC RBRF
20kV/100V
Y
Y
59N
ROV2 PTOV
90
TR8 ATCC
Mont.
DRP RDRE
© Copyright 2011 ABB Power Grids. All rights reserved
RET650 A01A - 2 Winding Transformer protection 10AI (8I+2U)
50/51
3I>
52PD
PD
OC4 PTOC
CC RPLD
IN>
51N
EF4 PTOC
51/67
3I>
52PD
PD
OC4 PTOC
CC RPLD
3U0>
IN>
51N/67N
EF4 PTOC
27
U<
59
U>
U
UV2 PTUV
OV2 PTOV
Meter.
Meter.
V MMXU
C MSQI
Function Enabled
in Settings
ANSI
IEC
IEC61850
1MRK 504 127-BUS B
49
Ith
50
3I>>
TR PTTR
PH PIOC
87N
IdN/I
87T
REF PDIF
T2W PDIF
49
Ith
TR PTTR
87N
IdN/I
REF PDIF
Meter.
Meter.
C MMXU
CV MMXN
Function Disabled in Settings
ANSI
IEC
ANSI
IEC
DNP
IEC60870-5-103
ANSI11000134_1_en.vsd
3Id/I
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret650

Table of Contents