Transformer protection RET650
Version 1.1 ANSI
reliability and an extended purchase portfolio. The logic
selector switches eliminate all these problems.
Selector mini switch VSGGIO
The Selector mini switch VSGGIO function block is a
multipurpose function used for a variety of applications,
as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol
on the single line diagram (SLD) on the local HMI.
IEC 61850 generic communication I/O functions
DPGGIO
The IEC 61850 generic communication I/O functions
(DPGGIO) function block is used to send double
indications to other systems or equipment in the
substation. It is especially used in the interlocking and
reservation station-wide logics.
Single point generic control 8 signals SPC8GGIO
The Single point generic control 8 signals (SPC8GGIO)
function block is a collection of 8 single point commands,
designed to bring in commands from REMOTE (SCADA) to
those parts of the logic configuration that do not need
extensive command receiving functionality (for example,
SCSWI). In this way, simple commands can be sent directly
to the IED outputs, without confirmation. Confirmation
(status) of the result of the commands is supposed to be
achieved by other means, such as binary inputs and
SPGGIO function blocks. The commands can be pulsed or
steady.
AutomationBits AUTOBITS
The Automation bits function (AUTOBITS) is used to
configure the DNP3 protocol command handling.

10. Logic

Tripping logic SMPPTRC (94)
A function block for protection tripping is provided for
each circuit breaker involved in the tripping of the fault. It
provides pulse prolongation to ensure a trip pulse of
sufficient length, as well as all functionality necessary for
correct co-operation with autoreclosing functions.
The trip function block includes functionality for breaker
lock-out.
Trip matrix logic TMAGGIO
Trip matrix logic TMAGGIO function is used to route trip
signals and other logical output signals to different
output contacts on the IED.
ABB Power Grids
TMAGGIO output signals and the physical outputs allows
the user to adapt the signals to the physical tripping
outputs according to the specific application needs.
SEMOD158756-5 v5
Configurable logic blocks
A number of logic blocks and timers are available for the
user to adapt the configuration to the specific application
needs.
• OR function block.
• INVERTER function blocks that inverts the input signal.
• PULSETIMER function block can be used, for example,
SEMOD55850-5 v3
• GATE function block is used for whether or not a signal
• XOR function block.
SEMOD176462-4 v5
• LOOPDELAY function block used to delay the output
• TIMERSET function has pick-up and drop-out delayed
• AND function block.
• SRMEMORY function block is a flip-flop that can set or
SEMOD158591-5 v4
• RSMEMORY function block is a flip-flop that can reset or
M12275-3 v5
Boolean 16 to Integer conversion B16I
Boolean 16 to integer conversion function (B16I) is used to
transform a set of 16 binary (logical) signals into an
integer.
Boolean 16 to Integer conversion with logic node
representation B16IFCVI
M15321-3 v7
Boolean 16 to integer conversion with logic node
representation function (B16IFCVI) is used to transform a
set of 16 binary (logical) signals into an integer.
© Copyright 2011 ABB Power Grids. All rights reserved
for pulse extensions or limiting of operation of outputs.
should be able to pass from the input to the output.
signal one execution cycle.
outputs related to the input signal. The timer has a
settable time delay.
reset an output from two inputs respectively. Each block
has two outputs where one is inverted. The memory
setting controls if the block's output should reset or
return to the state it was, after a power interruption.
set an output from two inputs respectively. Each block
has two outputs where one is inverted. The memory
setting controls if the block's output should reset or
return to the state it was, after a power interruption.
Reset input has priority.
1MRK 504 127-BUS B
M11396-4 v10
SEMOD175725-4 v3
SEMOD175781-4 v4