ABB Relion 650 Series Product Manual page 31

Transformer protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Transformer protection RET650
Version 1.1 ANSI
Type tests according to standards
Table 16. Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst disturbance test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Radio frequency interference tests
• Conducted, common mode
• Radiated, amplitude-modulated
Fast transient disturbance tests
• Communication ports
• Other ports
Surge immunity test
• Communication
• Other ports
Power frequency (50 Hz) magnetic field
• 3 s
• Continuous
Power frequency immunity test
• Common mode
• Differential mode
Voltage dips and short interruptions
ABB Power Grids
GUID-2794AAD0-DBFE-476D-BAD1-A8D0ECFE9C9C v4
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
20 V/m (rms), f=80...1000 MHz and f=1.4...2.7
GHz
4 kV
4 kV
1 kV line-to-ground
2 kV line-to-ground, 1 kV line-to-line
1000 A/m
100 A/m
300 V rms
150 V rms
Dips:
40%/200 ms
70%/500 ms
Interruptions:
0-50 ms: No restart
0...∞ s : Correct behaviour at power down
© Copyright 2011 ABB Power Grids. All rights reserved
1MRK 504 127-BUS B
Reference
IEC 61000-4-18
IEC 60255-22-1, level 3
ANSI C37.90.1-2002
IEC 61000-4-2
IEC 60255-22-2, level 4
ANSI C37.90.3-2001
IEC 61000-4-6
IEC 60255-22-6, level 3
IEC 61000-4-3
IEC 60255-22-3, level 3
ANSI C37.90.2-2004
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2002
IEC 61000-4-5
IEC 60255-22-5, level 3/2
IEC 61000-4-8, level 5
IEC 60255-22-7, class A
IEC 61000-4-16
IEC 60255-11
IEC 61000-4-11
IP15778-1 v1
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion ret650

Table of Contents