Check the condensed water drainage:
a
Pour about 2 liters of water into the indoor unit
drain pan as shown in the picture.
b
When the electric cable connection is completed
•
Turn on the indoor unit and outdoor unit.
•
Operate in the Cool mode.
CAUTION
•
Only in the Cool mode, you can check the correct
operation of the drain pump.
When the electric cable connection has not been
completed
•
Remove the control box cover of the indoor unit.
•
Connect the power supply (220~240V, 50 Hz) to the
L and N terminals.
•
Reassemble the control box cover and turn on the
indoor unit.
CAUTION
•
When the float switch is not detected due to
insufficient water on the drain pan, the drain
pump will not work.
•
If the power supply is directly connected to the L
and N terminals, communication error message
might appear.
•
After completing the drainage check, turn the
unit off and disconnect the power supply.
•
Reassemble the control box cover.
c
Check whether the drain pump works correctly.
d
Check whether the drainage is performing correctly
at the end of the drain pipe.
e
Check for leakage at the drain pipe and drain pipe
connection part.
f
When leakage occurs, check whether the indoor
unit is level and check the drain hose connection
part, drainpipe connection part and drain pump
connection.
g
When the drainage check is completed and the
condensed water remains on the drain pan, remove
the water.
Step 12 Connecting the power and
communication cables
CAUTION
•
Always remember to connect the refrigerant pipes
before performing the electric connections.
When disconnecting the system, always disconnect the
electric cables before disconnecting the refrigerant
pipes.
•
For the product that uses the R-32 refrigerant, be
cautious not to generate a spark by keeping the
following requirements:
–
Do not remove the fuses with power on.
–
Do not disconnect the power plug from the wall
outlet with power on.
–
It is recommended to locate the outlet in a high
position. Place the cords so that they are not
tangled.
•
Always remember to connect the air conditioner to
the grounding system before performing the electric
connections. Use a crimp ring terminal at the end of
each wire.
The indoor unit is powered through the outdoor unit by means
of a H07 RN-F connection cable (or a more power model), with
insulation in synthetic rubber and a jacket in polychloroprene
(neoprene), in accordance with the requirements specified in
the standard EN 60335-2-40.
1
Remove the screw on the electrical component box and
remove the cover plate.
2
Route the connection cord through the side of the indoor
unit and connect the cable to the terminals refer to the
figure below.
3
Route the other end of the cable to the outdoor unit
through the ceiling & the hole on the wall.
4
Reassemble the electrical component box cover, carefully
tightening the screw.
English