Contents 11. Precautions ..................................................1-1 Installing the air conditioner ....................1-2 Power supply and circuit breaker ..........................1-3 During operation ........................1-4 Disposing of the unit ..............................1-5 Others 12. Product Specifications ............................................... 2-1 The Feature of Product ...........................
An all pole disconnection from the power supply must be incorporated in the fixed wiring with a contact opening of >3mm. ● Do not extend an electric cord to the air conditioner. ● The air conditioner must be plugged in after you complete the installation. Samsung Electronics...
● Young children or infirm persons should be always supervised when they use the air conditioner. ● Max current is measured according to IEC standard for safety. ● Current is measured according to ISO standard for energy efficiency. Samsung Electronics...
– Long piping – • Maximum length : 50m – • Maximum height : 30m ■ Convenient Control Functions – Auto Change Over – Central Controller(Optional) : Can Control up to 16 units individually – Group Control – Weekly program(Optional) Samsung Electronics...
✳ Setting is not required if you must Push the button to set the display panel to a value which has a default. Every time you push the button, the display panel reads . . . repeatedly. Samsung Electronics...
Page 15
If all lamps of indoor unit are flickering, Plug out, plug in power plug again and press ON/OFF key to retry. If the unit is not working properly or all lamps are continuously flickering after setting the option code, see if the correct option code is set up for its model. Samsung Electronics...
Remark 4) After disassembling 2 places indicating screws, detach Fan Motor and Blower from the set. 1) After disassembling 1 Indicating screw, Control In detach the Cover control. 2) Detach the Motor-Fan and Sensor Connector from the PCB. Samsung Electronics...
Page 23
Procedure Remark 3) Disassemble 4 indicating screws and detach Control In from the set. ✳ Work is possible when Disassembling the Drain Pan Ass'y Cabi Bottom Blower. 1) Disassemble 6 indicating screws and detach Ass'y Cabi Bottom Drain. Samsung Electronics...
Page 24
3) Disassemble 6 indicating screws and detach the Drain Pan. (3 screws each at left and right side) ✳ Work is possible when Disassembling Evap the Ass'y Drain Pan. 1) Disassemble 5 indicating screws to detach Cover Pipe. Samsung Electronics...
Page 25
Procedure Remark 2) Disassemble Sensor on the Evap. 3) Disassemble 2 indicating screws which are in the near of Hanger Plate to detach the Evap. (1 screw each at left and right side) It needs 2 peoples. 4-10 Samsung Electronics...
Temperature Sensor Ventilator Wired Remote Controller Power Drain Pump “ External Control(S/W Part) Hot Coil & ‘ Indoor Fan(SSR) Display Power External Control(Display Part) Transformer Out HALL IC Main Power In MICOM Download Power Indoor/Outdoor Communication Transformer In 10-1 Samsung Electronics...
Page 56
Display : SMW200-11(WHT) : SMW200-11(WHT) Power : YW396-03AV(WHT) External Control(Display Part) : SMW250-04(RED) Transformer Out : YW396-03AV(WHT) HALL IC : SMW250-03(BLU) Main Power In : YW396-03AV(BLU) MICOM Download : SMW200-10(WHT) Power : YW396-03AV(BLU) Indoor/Outdoor Communication : YW396-02(RED) Transformer In : SMW250-03(RED) Samsung Electronics 10-2...
Page 57
Main Power In Transmitter Power(12V) Outdoor Fan 1 Discharge Temperature Sensor Outdoor Fan 2 Outdoor Temperature Sensor Compressor Output Outdoor Pipe Temperature Sensor 4-Way Valve Output Low Pressure S/W Bypass & Communication Transformer In Transformer Out 3 Phase Check 10-3 Samsung Electronics...
3. To adjust the temperature, press the buttons one or more times until the required temperature is displayed. Possible temperatures are between 18˚C and 30˚C inclusive. 11-1 Samsung Electronics...
Page 60
Possible temperatures are between 16˚C and 30˚C inclusive. 4. Select the fan speed by pressing the button one or more times until the intended value is displayed : ➔ ➔ Automatic(rotated : Medium High Samsung Electronics 11-2...
2. To select the FAN mode, press the button until is displayed at the top of the wired remote controller. 3. Select the fan speed by pressing the button one or more times until the intended value is displayed: Medium High 11-3 Samsung Electronics...
■ External Control • You must adjust the K11 when you use external control. Switch No. Switch ON Switch OFF No use of external control Use of external control K 1 K 2 K 3 K 4 SW07 Samsung Electronics 11-4...
Page 63
Connector No. Function PIN #1 and #2 of CN81(RED) +12V Out if any error occurs PIN #3 and #4 of CN81(RED) +12V Out when the compressor is operating Error Display Comp. Status Display Sub. PCB 220V CN81(RED) 11-5 Samsung Electronics...
Filter Sign indicator when the time to clean the air filter. • Duct type air conditioner does not have function of adjusting air flow direction. Therefore, the function is not operated even if you press the button. Samsung Electronics 11-6...
Counts of Indoor 10 11 12 13 14 15 Unit Installation Numbers of the switch ● Example : When the installed indoor unit is one, control the arrow of switch forward to ‘0’ or ‘1’ as figure. 12-1 Samsung Electronics...
Adding refrigerant at Adding refrigerant at Displays data Reset heating mode cooling mode Test operation at Test operation at heating mode cooling mode Pump Down for recovery of refrigerant ✳ Use the K1 only for heat pump models. Samsung Electronics 12-2...
Wired remote controller Error of communication between the indoor unit and the wired errors remote controller Master wired remote controller ↔ Slave wired remote controller COM1/COM2 Cross-installed error Error of setting option for wired remote controller COM2 12-3 Samsung Electronics...
5. Error of reverse phase 6. Compressor down due to 6'th detection of freezing Detection of the float switch Error of setting option switches for optional accessories EEPROM error EEPROM option error : On : Flickering : Off Samsung Electronics 12-4...
Page 69
The order of priority : E1 → E2 → E3 → E5 → P0 → P1 → P4 → P5 → P9 → t1 → t2 → t3 → tu → to → G4 → G5 → E3 → qx → rx → vx → K1, K2, K3, K4, K5 The order of priority : - In case that the same error displays from multi-indoor units, the one having the faster address has the priority. 12-5 Samsung Electronics...
K4 3 times. At this time, is occurred the difference between the out temp. and data? PCB and sensor are normal. To perform the test operation by use of K2 Reoperation after PCB replacement Samsung Electronics 12-6...
Page 71
K4 2 times. At this time, is occurred the difference between the out temp. and data? PCB and sensor are normal. To perform the test operation by one of K2 Reoperation after PCB replacement 12-7 Samsung Electronics...
Page 72
K4 1 times. At this time, is occurred the difference between the out temp. and data? PCB and sensor are normal. To perform the test operation by use of K2 Reoperation after PCB replacement Samsung Electronics 12-8...
Page 73
PCB, and find the indoor unit preventing communication through connecting the communication connectors each by each, and then replace the indoor unit PCB after line check. Good +0.7V -0.7V 12-9 Samsung Electronics...
Page 74
PCB after line check Samsung Electronics 12-10...
Page 75
PCB about AC220V? Does the water level decrease? Replace the drain pump Replace the indoor unit PCB Normal operation Replace the drain pump Note : E3 error should be released when indoor unit power is reset. 12-11 Samsung Electronics...
4-Way Valve Pipe Temperature Sensor Control part MICOM Sensor Control Part Bypass Valve Outdoor Load 3 Phase 3 Phase Input Control Part Check part Power Supply Communication Room/Pipe/Discharge Part Part 1 Temperature Sensor Indoor Communication Central Control Samsung Electronics 13-1...
Page 79
It occurs when the drain pump is plugged out or it is out of order. Check the power of the drain pump and the position of the drain hose, and when the pump is faulty, contact the drain pump manufacturer. Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems.
Page 80
Set up a sun blind over the outdoor unit and clear the neighboring obstacles from the outdoor unit to provide good ventilation. When it goes off frequently during a heat wave, it would prevent the turn-off and increase the cooling capacity cleaning the outdoor unit or spraying some water to the heat exchanger. Samsung Electronics 14-4...
Page 81
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
5. When you have finished, insert the filter into the unit. 6. Clean the outdoor unit with a vacuum cleaner or a brush once a month. Note : • After cleaning the air conditioner, press the Filter Reset button. Wireless Remote Controller Wired Remote Controller Samsung Electronics 14-6...
Electric and earth work shall meet the "Electric Facility Technology Standard" and the "Internal Wire Regulation" of the Electric Business Laws. ■ Inspection & Trial Run Upon completion of the tests, you shall make a trial run while you explain the main functions of the air conditioner to finish the installation. 14-7 Samsung Electronics...
183kgf . cm with a torque wrench. A(gas) 7) Check for gas leakage. B(liquid) - At this time, especially check for gas Valve stem leakage from the 3-Way valve’s stem nuts, Stem cap and from the service port cap. Samsung Electronics 14-8...
At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign material entering. • Make sure you do not bend the connection pipes in the middle and store together with the cables. • Move the indoor and outdoor units to a new location. 14-9 Samsung Electronics...