Installation Procedure
1) SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
Fan stops or operates Ultra low in Cooling when thermostat is off.
2) SEG8
Even if you set the Use of drain pump option to 0, it is automatically set to 2 (the drain pump is used with 3 minute delay).
3) SEG11
Compensation of the WindFree fan RPM option adjusts 20 rpm per 1 step.
4) SEG14
Example: When installing DPM (1 Outdoor unit with 4 indoor units)
Condition
External control
Level control
Default
Disuse
Use (Indoor 3)
Use (Indoor 4)
5) SEG18
If you set the Maximum filter usage time option to a value other than 2 and 6, it is automatically set to 2 (1000 hours).
6) SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
7) SEG21
8) SEG23
Soft Off: The indoor unit turns off its operation at the indicated time in the table for Installation Option after its final motion
detection. But, it turns on again if the MDS detects motion.
Hard Off: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users should control to
turn on the indoor unit with remote control, etc.
26
English
Indoor 1
Use
4
Disuse
Not set (0)
Use
Not set (0)
SEG14 Setting
Indoor 2
Indoor 3
Not set (0)
Not set (0)
Not set (0)
Not set (0)
1~3
Not set (0)
Not set (0)
Result
Indoor 4
Slave (All)
Master (Indoor 1),
Not set (0)
Slave (Indoor
2,3,4)
Not set (0)
Slave (All)
Master (Indoor 4),
5~7
Slave (Indoor 1,2,3)