Table 12
Power Module Specifications
Parameter
SAFETY CERTIFICATIONS
SDU DC UPS System*
*The SDU DC UPS system includes a power module (SDU 10-24B or SDU 20-24B)
Note 1-
WARNING - Risk of explosion.
The SDU 24-BATEM has not been evaluated for use in any hazardous location and cannot be installed
in a Class I, Div 2 or Class I, Zone 2 hazardous location. Do not install in a hazardous location!
SDU 10-24B
Hazardous Locations (except SDU 24-BATEM):
Groups A B C D T4, UL/CSA 60079-0, UL/CSA 60079-7,
UL/CSA 60079-15 Class I, Zone 2, Groups IIC
EN IEC 60079-0, EN IEC 60079-7, EN IEC 60079-15
SDU 10-24B, SDU 20-24B - II 3 G Ex ec nC IIC T4 Gc, UL 22 ATEX 2553X,
SDU 24-BATB - II 3 G Ex ec IIC T4 Gc, UL 22 ATEX 2553X,
cULus Listed: UL/CSA 61010-1, UL/CSA 61010-2-201
cRUus: UL Recognized Component UL/CSA 62368-1, UL/CSA 60950-1
CE LVD / UKCA EE (Safety) Regulations 2016 –IEC/EN 62368-1,
IEC/EN 61010-1, IEC/EN 61010-2-201 (CB Certified IEC/EN 60950-1)
CE/UKCA EMC - EN 62040-2 Category C2, EN 55032, EN 55011,
EN 55035, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3,
EN 61000-6-4, EN 61326-1, EN61000-3-2, EN 61000-3-3
See Note 1 below- UL Recognized UL121201/CSA 213 Class I,
See Note 1 below- ATEX/UKCA – EN IEC 60079-0, EN IEC 60079-7,
Models SDU 10-24B, SDU 20-24B - II 3 G Ex ec nC IIC T4 Gc
and a battery module (SDU 24-BATB or SDU 24-BATEM).
Catalog Number
Recognized - UL121201/CSA 213 Class I, Division 2
UKCA and CE Ex Certified:
UL22UKEX2393X
UL22UKEX2393X
Division 2 Groups A B C D T4
EN IEC 60079-15
Model SDU 24-BATB - II 3 G Ex ec IIC T4 Gc
SDU 20-24B
Page: 17