Daikin FVXM50A3V1B Installer's Reference Manual page 24

Split system air conditioners
Hide thumbs Also See for FVXM50A3V1B:
Table of Contents

Advertisement

6
|
Unit installation
To determine the minimum floor area
Installer reference guide
24
In bathrooms.
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
Spacing. Mind the following requirements:
A
≥50
A Front view
B Side view
Do not install the unit more than 60 mm above the floor.
The system using R32 refrigerant is restricted with respect to the total refrigerant
charge and/or the floor area that is served.
To determine the total refrigerant charge (m) in the system see the Installation
manual of the outdoor unit.
Note: It is not allowed to install an indoor unit in a room with area <A
Depending on the total refrigerant charge (m), the minimum floor area is (A
INFORMATION
Use following table and graph for CVXM-A9 and FVXM-A9.
If the required exact value for the total refrigerant charge in the system (m) is not
listed below, use the closest higher value.
The total refrigerant charge (m), the minimum floor area is (A
depends also on room height (H) and if the unit is installed ABOVE or UNDER
ground level.
If indoor unit is installed in room ABOVE ground level
m (kg)
≤1.842
1.843
1.9
2.0
2.1
2.2
2.3
2.4
2.5
B
≥50
A
min
H=2.2 m
H=2.0 m
No limitations
3.64
4.00
3.75
4.13
3.95
4.34
4.15
4.56
4.34
4.78
4.54
4.99
4.74
5.21
4.94
5.43
(65)
(mm)
 (m²).
min
) limitation
min
2
(m
)
H=1.8 m
4.45
4.58
4.83
5.07
5.31
5.55
5.79
6.03
CVXM-A, FVXM-A, CVXM-A9, FVXM-A9, FVXTM-A