WARNING
CVXM-A and FVXM-A Floor Standing range is allowed to be combined ONLY with
systems with total refrigerant amount ≤1.842  kg. Therefore in case of
combination with outdoor units 3MXM40 or 3MXM52, the total liquid refrigerant
piping length of the installation MUST be ≤30 m.
For CVXM-A9 and FVXM-A9 refer to
4
area" [
 24].
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
Install power cables at least 1  meter away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1  meter may NOT be
sufficient.
Fluorescent lights. When installing a wireless remote control (user interface) in a
room with fluorescent lights, mind the following to avoid interference:
-
Install the wireless remote control (user interface) as close as possible to the
indoor unit.
-
Install the indoor unit as far as possible from the fluorescent lights.
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone and the location is selected according the
applicable legislation.
Air flow. Make sure nothing blocks the air flow.
Drainage. Make sure condensation water can be evacuated properly.
Wall insulation. When conditions in the wall exceed 30°C and a relative humidity
of 80%, or when fresh air is inducted into the wall, then additional insulation is
required (minimum 10 mm thickness, polyethylene foam).
Wall or floor strength. Check whether the wall or the floor is strong enough to
support the weight of the unit. If there is a risk, reinforce the wall or the floor
before installing the unit.
Do NOT install the unit in the following places:
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may
shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
In places where the unit would be in the path of direct sunlight.