• When performing piping work, do not mix air except for specified refrigerant in
refrigeration cycle. It causes capacity down, and risk of explosion and injury due to
high tension inside the refrigerant cycle.
• If the refrigerant comes in contact with a flame, it produces toxic gases and fire.
• Do not add or replace refrigerant other than specified type. It may cause product
damage, burst and injury, etc.
• Ventilate the room immediately in the event of a refrigerant gas leakage during
installation. Be careful not to allow contact of the refrigerant gas with a flame as this will
cause the generation of toxic gases and fire.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before
connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
• Do not leak refrigerant while piping work for an installation or re-installation, and while
repairing refrigeration parts.
Handle liquid refrigerant carefully as it may cause frostbite.
• Under no circumstances shall potential sources of ignition be used in the searching or
detection of refrigerant leaks.
• A halide torch (or any other detector using a naked flame) shall not be used.
• Electronic leak detectors may be used to detect refrigerant leaks but, the sensitivity
may not be adequate, or may need re-calibration. (Detection equipment shall be
calibrated in a refrigerant-free area.)
• Ensure that the detector is not a potential source of ignition and is suitable for the
refrigerant used.
• Leak detection equipment shall be set at a percentage of the lower flammable limit
(LFL) of the refrigerant and shall be calibrated to the refrigerant employed and the
appropriate percentage of gas (25% maximum) is confirmed.
• Leak detection fluids are suitable for use with most refrigerants but the use of
detergents containing chlorine shall be avoided as the chlorine may react with the
refrigerant and corrode the copper pipe-work.
• If a leak is suspected, all naked flames shall be removed/extinguished.
• If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be
recovered from the system, or isolated (by means of shut off valves) in a part of the
system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through
the system both before and during the brazing process.
When Servicing
• Contact the sales dealer or service dealer for a repair.
• Be sure to turn off the power before servicing.
• Turn the power OFF at the main power box (mains), wait at least 5 minutes until it
is discharged, then open the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of
wiring have been left inside the unit.