Site Survey; Calculating The Pipe System - Siemens FDA2 Series Planning, Mounting

Pipe system for aspirating smoke detectors
Table of Contents

Advertisement

4.1 Site survey

4.2 Calculating the pipe system

A6V11783979_en--_a
Survey the site where the aspirating smoke system is to be installed in order to
obtain key information for planning the pipe system.
Condition (material and surface) of:
Walls
Floors
Ceilings
Furniture
Decoration
Type of rooms in the fire section
Type of heating
Underfloor heating
Ceiling heating
Radiant heaters
Air conditioning system
Cavities
False floor
False ceiling
Ducts
Shafts
Room geometry in the fire zone
Demarcation of the fire zone
Availability of up-to-date construction plans
Dust load in the environment to be monitored
The data acquired on site provides the basis for calculating the pipe system using
the software 'FXS2056 ASD Asyst‑Tool V3'.
The software 'FXS2056 ASD Asyst‑Tool V3' must be used to perform the
calculation prior to every installation.
4
Planning
Site survey
27 | 48