Siemens SIMATIC ET 200SP Manual page 20

Analog input module ai 8xrtd/tc 2-wire hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters
Value range
Hardware interrupt
low limit 2
3
Low limit 2
3
Potential group
Diagnostics: Missing supply voltage L+: Detection per module or alarm per channel
1
Interference frequency suppression: Interfering signals at 400 Hz are automatically included in the filtering at 50 Hz.
2
Due to the limited number of parameters at a maximum of 244 bytes per ET 200SP station with a PROFIBUS GSD
3
configuration, the configuration options are restricted. If required, you can still assign these parameters using data
record 128 as described in the "GSD file PROFINET IO" column (see table above). The parameter length of the
I/O module is 24 bytes.
Only for configuration with PROFIBUS GSD file: The set reference junction is used with the additional parameter
4
"Kx Reference junction activated" in the case of "Enable". In the case of "Disable", "No reference channel mode" is used
for RTD and "Fixed reference temperature" is used for TC.
Note
Unused channels
"Deactivate" unused inputs in the parameter assignment to shorten the cycle time of the
module.
A deactivated input always returns the value 7FFF
Analog input module AI 8xRTD/TC 2-wire HF (6ES7134-6JF00-0CA1)
Manual, 02/2014, A5E32942580-AA
Disable
Enable
Value
Use potential group of the
left module
Enable new potential group
Default
Reconfigu-
ration in
RUN
Disable
Yes
-2000
Yes
Use potential group
No
of the left module
.
H
Parameters/address space
4.2 Scalable measuring range
Scope with configuration
software, e.g. STEP 7
(TIA Portal)
GSD file
GSD file
PROFINET
PROFIBUS
IO
DP
Channel
-
Channel
-
Module
Module
3
19