5.3 Crimping an OT or DT Terminal

Requirements for OT/DT Terminals
Issue 02 (2022-12-20)
Type
● If the ground point
on the enclosure is
used, three-core
(L1, L2, and L3)
outdoor cables and
M12 OT/DT
terminals (L1, L2,
and L3) are
recommended.
● If the ground point
in the maintenance
compartment is
used, four-core (L1,
L2, L3, and PE)
outdoor cables,
M12 OT/DT
terminals (L1, L2,
and L3), and M10
OT/DT terminals
(PE) are
recommended. You
do not need to
prepare a PE cable.
If a copper cable is used, use copper wiring terminals.
If a copper-clad aluminum cable is used, use copper wiring terminals.
If an aluminum alloy cable is used, use copper-to-aluminum wiring terminals,
or aluminum wiring terminals with copper-to-aluminum washers.
Copyright © Huawei Technologies Co., Ltd.
Conductor
Outer
Cross-Sectional
Diameter
Area
● Copper cable:
24–66 mm
– S: 95–150
2
mm
– S
≥ S/2
p
● Aluminum
alloy cable or
copper-clad
aluminum
cable:
– S: 150–240
2
mm
– S
≥ S/2
p
5 Installing Cables
Source
Prepared by
the
customer
43